REFRIGERANT PIPING AND REFRIGERANT CHARGE
13.3.3.
SUSPENSION OF REFRIGERANT PIPING
Suspend the refrigerant piping at certain points and prevent
the refrigerant piping from touching the weak part of the
building such as wall, ceiling, etc…
(If touched, abnormal sound may occur due to the vibration
of the piping. Pay special attention in case of short piping
length).
Do not fix the refrigerant piping directly with the metal fittings
(The refrigerant piping may expand and contract).
Some examples for suspension method are shown below.
For Suspending
Heavies
For Piping Along The
Wall
For Instant Installation
Work
13.3.4.
TIGHTENING TORQUE
1. Flaring connections (smaller than a diameter of Ø19.05)
are generally used. However, if incorrect flaring is
performed, it will cause serious refrigerant leakage.
2 Shape after Flaring, it should be rectangular and flat, and
no uneven thickness, cracks and scratches should exist.
Nominal
Dia.
Tube Dia.
Ød
Dimension
A
1/4
6.35
9.00
3/8
9.52
13.00
1/2
12.70
16.20
5/8
15.88
19.40
3/4
19.05
23.30
When tightening the flare nuts, use two spanners, as shown
in the figure.
The required tightening torque is as follows:
§
Indoor Units and CH Unit
Pipe Size
Tightening Torque (Nm)
Ø 6.35 mm
20
Ø 9.53 mm
40
Ø 12.7 mm
60
Ø 15.88 mm
80
Ø 19.5 mm
100
§
Outdoor Units
Operation of the stop valve should be performed according
to the below figure.
B
RAS-FSG(1)
A
Flare
Screw of Flange
C
Liquid
16
40
-
9
5HP
Gas
44
100
-
9
Liquid
29.5
40
-
9
8HP
Gas
49
-
40 to 60
9
Liquid
29.5
40
-
9
10HP
Gas
49
-
40 to 60
9
Liquid
29.5
80
-
9
16HP
Gas
49
-
83 to 120
9
Liquid
29.5
80
-
9
20HP
Gas
49
-
83 to 120
9
Liquid
44
100
-
9
24HP
Gas
49
-
83 to 120
9
Liquid
44
100
-
9
30HP
Gas
49
-
83 to 120
9
B
RAS-FXG(1)
A
Flare
Screw of Flange
C
Liquid
29.5
40
-
9
Gas High
49
100
-
9
8HP
Gas Low
59
41 to 60
9
Liquid
29.5
40
-
9
Gas High
49
100
-
9
10HP
Gas Low
59
41 to 60
9
Liquid
44
80
-
9
Gas High
49
-
83 to 120
9
24HP
Gas Low
59
84 to 120
9
Liquid
44
100
-
9
Gas High
49
-
83 to 120
9
30HP
Gas Low
59
84 to 120
9
1~15m
Fire-Proof
Section
Treatment
Indoor Unit
+0.0
–0.4
Allen key
(To open or close
the Spindle valve)
C
Check Joint
(Only the charging
hose can be
connected. Tighten
the cap with a
torque of C Nm)
A
CAP
(Tighten the cap with a
torque A Nm
B
CAP
(Tighten the cap with a
torque B Nm when it is Flare
Nut, or apply B Nm torque to
screw of flange)
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...