GF 9950-10 Six Channel Transmitter
Start-Up Guide
Relay Module Wiring
3-9950.393-1 and 3-9950.393-2
Relay 1: The alarm is OFF during normal operation, and will
go ON when relay energizes according to 9950
Relay settings.
Relay 4: The valve is ON during normal operation, and will
go OFF when relay energizes according to 9950
Relay settings.
NO = normally open (closes when energized)
NC = normally closed (opens when energized)
Mechanical Relays Rating:
5A 250 VAC, 5A 30 VDC
Solid State Relays Rating:
50 mA 30V AC/DC
(for 309950.393-2 relay 1 & 2)
3-9950.393-3
The alarm is OFF during normal operation, and will go ON when the
relay energizes according to 9950 Relay settings.
Binary input 4 will be ON when the tank level is above the level
switch, Binary Input 4 will be OFF when the tank level is below the
level switch.
Binary Input Ratings
Maximum Input voltage
(without damage)
30 VDC
Minimum Input voltage
(without damage)
-5 VDC
(no operation below 0 VDC)
Maximum input voltage for
signal “Off” (low or "0")
1.5 VDC
Minimum input voltage
for signal “On” (high or "1")
3.0 VDC
Maximum current draw for
signal “0” (low)
<500
μ
ADC
Minimum current draw
for signal “1” (high)
500
μ
A
Typical current draw
for signal “1” (high)
6.0 mA at 30 VDC, 4.8 mA at 24 VDC,
2.4 mA at 12 VDC, 1.0 mA at 5 VDC
•
Terminals accept 12 to 22 AWG wire.
•
Strip 10 to 12 mm (0.4 to 0.5 in.) of insulation from wire tips and tin bare ends to eliminate fraying.
•
Insert wire tip or ferrule completely into the terminal and secure with the screw.
•
Do not allow any AC leads that may be connected to the internal relays to come in contact with low voltage wiring.
NO 1
N/C 1
COM 1
NO 2
N/C 2
COM 2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
NO 3
N/C 3
COM 3
NO 4
N/C 4
COM 4
AC or DC
power
Valve
Flow
AC or DC
power
ALARM!
3-9950.393-1
N/O 1
N/C 1
COM 1
SW4
SW COM
N/O 2
N/C 2
COM 2
SW3
SW2
SW1
X
RELAY 1
RELAY 2
BINARY INPUT 3
BINARY INPUT 1
No Connection
BINARY INPUT 2
BINARY INPUT 4
AC or DC
power
ALARM!
Level
Level Switch
9950.393 Internal Power
N/O 1
N/C 1
COM 1
SW4
SW COM
N/O 2
N/C 2
COM 2
SW3
SW2
SW1
X
RELAY 1
RELAY 2
BINARY INPUT 3
BINARY INPUT 1
No Connection
BINARY INPUT 2
BINARY INPUT 4
AC or DC
power
ALARM!
Level
Level Switch
DC power
+
-
9950.393 External Power
3-9950.393-3 Internal Power
3-9950.393-3 External Power
If an externally powered sensor is connected with the
3-9950.393-3 module, set the power switch to the EXT
position. The module can power external sensors by
switching the power switch to the INT position. Maximum
power that can be drawn from the module is 6mA at 30 VDC.