21
GF 9950-10 Six Channel Transmitter
The following pages list the sensor-speci
fi
c settings for each sensor type. The user can con
fi
gure the
unit to run each channel on different parameters if needed.
FLOW Setup Checklist
1. Make sure FLOW sensor type is selected
(Refer to System Setup Menu, page 9).
2. Set the Units of Measurement.
3. Set Sensor Type (Freq or S
3
L) and if 515 or 525, select Yes.
4. If LOOP is used, set the minimum and maximum 4 to 20 mA setpoints.
5. Set K-Factor (pulses per Unit Volume) from Flow Sensor manual.
6. Set Totalizer factor.
7. Set Last Cal Date and initials.
8. If applicable, set up relay functions for your application.
Sensor-Speci
fi
c Menus
Flow
VIEW Mode Menu
View Measurement 2 displays the primary value and the channel name. This screen does not time out.
Displays the Permanent Totalizer and Resettable Totalizer for each FLOW channel
(note the "P" indicating Permanent and "R" for Resettable) Pressing
►
will prompt you to reset.
Pressing
►
again will verify YES or NO. Pressing ENTER will reset the totalizer.
CH 1 TOTALIZER
R 40560.0 ->
P 40560.0
LITERS
CH1
50.30
FLOW
CH2
987.9
FLOW
GPM
GPM
100.00
0.00
0.00
100.00
Displays the
fl
ow rate and the resettable
or permanent totalizer below. This is the
normal display and does not time out.
CH1
50.30
40560.0
987.9
65.5
CH2
GPM
R
GPM
R
0.00
0.00
100.00
100.00
INPUT Menu
CHANNEL 1
FLOW
NAME
CH1 FACTORY
FACTORY
TYPE
CH1 FLOW
NONE
SOURCE
SETUP
CHANNEL 1
ENTER
Press ENTER to start assigning sensors to each channel.
Use the
▲
and
▼
arrow to go to any of the six channels directly.
NOTE: Display only available when the 9950 is in FACTORY mode.
Press the
►
arrow, use the
▲
and
▼
arrow to select which TYPE of sensor will be assigned to the
channel(s) (1-6).
Press ENTER to save sensor type.
Press the
►
arrow, using the
▲
or
▼
to select the INPUT source to the channel.
To change sensor selection after its been assigned, change the source to NONE, then the sensors can be
reassigned.
English, French, German, and Spanish Only. If desired, a custom name can be entered.
Enter 17-character string.
Default = FLOW
If the
fl
ow sensor is self powered such as a 515/525, select YES.
Select NO if an open connector such as 2536/2540/2100
fl
ow sensor is being used.
Default = YES
Select the FLOW RATE UNIT from the pull down menu.
Custom units can be created and used.
The last character sets the timebase: S (seconds) M (minutes) H (hours) D (days).
Default = GPM
NOTE: Screen will only appear if CUSTOM is selected from previous menu.
English, French, German, and Spanish Only. Display visible only when FLOW UNITS CUST/S, CUST/M,
CUST/H, CUST/D is selected. Allows user to set custom
fl
ow rate units for primary measurement. CUST/S,
M, H, D label can be adjusted to re
fl
ect to user's custom units.
CH 1 FLOW
YES
515/2536
CH 1 FLOW
FLOW UNITS
GPM
CH 1 FLOW
CUSTOM UNITS
CUST/S