GF 9950-10 Six Channel Transmitter
Warning / Caution / Danger
Indicates a potential hazard. Failure to follow all warnings
may lead to equipment damage, injury, or death
Electrostatic Discharge (ESD) / Electrocution Danger
Alerts user to risk of potential damage to product by ESD
Electrocution Danger
Alerts user to risk of potential of injury or death via
electrocution
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during installation
and service of GF products
NOTE / Technical Notes
Highlights additional information or detailed procedure
• Please read entire manual before unpacking, setting up or
operating this equipment. Adhere to all danger, warning and
caution statements. Failure to do so could result in serious
injury to the operator or damage the equipment. Make sure the
protection provided by this equipment is not impaired, do not use
or install this equipment in any manner other than speci
fi
ed in
this manual.
• This unit is designed to be connected to equipment which can
be hazardous to persons and property if used incorrectly.
• Read and understand all associated equipment manuals and
safety warnings before using with this product.
• Remove power to unit before wiring connections.
• Wiring connections to this product should only be performed by
quali
fi
ed personnel.
• Do not use unit if front panel is cracked or broken.
Safety Information
Start-Up Guide
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
minimum
clearance
25 mm
(1 in.)
For future reference, for each installation, it is recommended to record the part number and serial number of each of the
components listed here:
Facility Tag Number or System ID (user assigned):___________________
Base unit
3-9950-____
S/N ___________________
Relay Module
3-9950.393-____
S/N ___________________
Single Channel Cond./Resist. Module
3-9950.394-____
S/N ___________________
Dual Channel 4-20 Current Loop Out. Module
3-9950.398-____
S/N ___________________
Dual Channel Conductivity Module
3-9950.394-2
S/N ___________________
Modbus Module
3-9950.395-M
S/N ___________________
Installation
Panel Mount Installation
panel
V+
FREQ
DATA
GND
V+
FREQ
DATA
GND
Loop1+
Loop1–
Loop2+
Loop2–
PWR+
PWR–
CH2
CH1
USB
RELAY MODULE
MODULE 1
MODULE 2
Made in U.S. from U.S. and imported parts
DC POWER
12-32 VDC
0.50A Max
DC Power
12-32 VDC
0.03A Max
Loop Voltage
N
L
100-240 V
A
C
~
50-60 Hz, 24V
A
Max
quick-clip
gasket on
front side
of panel
mounting
bracket
Allowable panel thickness 2.36 mm (0.093 in.) to 33 mm (1.31 in.)
Before commissioning the device, make sure the supply voltage matches the voltage speci
fi
cations on the nameplate.
For DC power input and Loop current regulated voltage, use UL60950-1 or UL61010-1 certi
fi
ed power supply.
Power supply shall also be rated for operation at 4000 m altitude. Provide a suitable switch or circuit breaker the installation.
This switch must be located close to the device (easily reached), and marked as a circuit breaker. The switch or circuit breaker to be
used for power disconnect shall be certi
fi
ed to IEC 60947-1 and IEC 60947-3, per IEC 61010-1, Clause 6.11.4.2.
Overcurrent protection (rated > 10 A) is required for the power cable.