31
GF 9950-10 Six Channel Transmitter
ON prevents relays from activating while making adjustments, and relays in PULSE mode will suspend
pulsing. Output is held until the user exits the CAL menu or turns it OFF.
Press the
►
arrow, using the
▲
or
▼
to select OFF/ON. Press ENTER to save.
Default = OFF
With process pressure at zero, press the
►
arrow, using the
▲
or
▼
to set zero point for measurement.
NOTE: Application must be OFF and have zero pressure to perform this operation.
Press the
►
arrow, using the
▲
or
▼
to enter the pressure reading from a external reference
NOTE: Allows a maximum offset of 5 PSI to be entered.
Resets calibration to factory default. After pressing
►
, select YES/NO.
Enter date of calibration (MM-DD-YYYY) and initials of calibrator (XX)
CAL Menu
CH 2 PRESSURE
HOLD OUTPUTS
OFF
CH 2 PRESSURE
CH 2 PRESSURE
CH 2 PRESSURE
RESET CAL ->
SET ZERO
CH2 ORP
12-31-2015 XX
LAST CAL
SET PRESSURE
Pressure
LEVEL/VOLUME Setup Checklist
1. Make sure LEVEL/VOLUME sensor type is selected.
(Refer to System Setup Menu, page 11)
2. Select Main Measurement (Level or Volume).
3. Set Units of Measurement for LEVEL display (FT, IN, M, CM).
4. If desired, set Units of Measurement for VOLUME display.
5. Set the minimum and maximum 4 to 20 mA setpoints.
6. Set Speci
fi
c Gravity.
7. Set Sensor Offset.
8. If VOLUME is used, set Shape.
9. Set Last Cal Date and initials.
10. If applicable, set up relay functions for your application.
Displays the level value and the volume
below. This is the normal display and
does not time out.
VIEW Mode Menu
View Measurement 3 displays the primary value and the channel name. This screen does not time out.
Level / Volume
CH1
25.0
LEVEL
CH2
42.0
LEVEL
FT
FT
10.000
0.0000
10.000
0.0000
CH1
25.0
78.5
20.0
99.0
CH2
FT
GAL
FT
GAL
10.000
0.0000
0.0000
10.000