49
GF 9950-10 Six Channel Transmitter
Total Pulse
RELAY Menu
(ALL) Select source for each Relay 1 - 4 (relay base unit) or RELAY A, B, C and D (external 8059 relay
module). Choose PRIMARY (CH 1-6), SECONDARY (CH 1-6), BINARY 1 - 4, DERIVED FUNCTION 1 - 4,
TIMER, or MULTIPLE. Secondary Values are only available for pH, Conductivity/Resistivity, Level, Salinity
and Dissolved Oxygen. Derived Functions are only available when Derived Functions (CH 1-4) are enabled in
the OPTIONS menu.
(ALL) Select the desired mode of operation to switch the Relay state (ON / OFF). Modes avaliable OFF, LOW,
HIGH, WINDow IN, WINDow OUT, PROP PULSE, VOL PULSE, PWM, TOTAL, USP and ERROR. (Refer to
page 18, Relay Modes). Default = OFF. When MODE is set to ERROR, relay energizes if sensor problem is
detected on any channel. ON DELAY delays the energizing of the relay until after the programmed delay time.
(FLOW) The relay will activate for the set pulse width once the speci
fi
c volume of
fl
uid is registered.
English, French, German, and Spanish only.
A custom label can be assigned to the relay for ease of identi
fi
cation.
(FLOW) (Shown only if TOTAL) Resettable value that, when exceeded, turns relay on.
Must reset Totalizer (in VIEW Mode) to clear relay.
Set maximum value.
Set the duration of the relay pulse in seconds.
Minimum 0.1 seconds, maximum 999.9 seconds.
Select YES to have the Red Backlight illuminate during relay activation.
Select NO to not have the Red Backlight activated by the relay activation.
Default backlight setting - NO
RELAY 1
m
TOTAL
A
MODE
R1 SET TOTAL
LITERS
100.00
RELAY 1
RELAY 1
LABEL
RELAY 1 ACTIVATE
%
NO
E
RED BACKLIGHT
RELAY 1
mA
TEST RELAY
Relay source display allows operator to scroll thru relay 1 -4 on base unit and A-D on the external relay module.
External relays that are located in the 8059 External Relay module are limited to the basic relay modes as shown in the chart.
RELAY 1
CH 1 PRIMARY
SOURCE
RELAY 1
OFF
MODE