GF 9950-10 Six Channel Transmitter
Measurement value of your sensor when its output is 20.00 mA.
Dampens display, output and relay response rates.
Select Low, Med, High, OFF.
Default = OFF
4 to 20 mA
CH2 4-20mA INPUT
20 mA VALUE
100.00
CH2 4-20mA INPUT
C
OFF
AVERAGE
INPUT Menu
CAL Menu
ON prevents relays from activating while making adjustments, and relays in PULSE mode will
suspend pulsing. Output is held until the user exits the CAL menu.
Press the
►
arrow, using the
▲
or
▼
to select OFF/ON. Press ENTER to save.
Default = OFF
Applies a linear offset to the measurement.
For single point calibrations, assign the average value of your process to STANDARD.
For two-point calibrations, assign the min or max value of your process to STANDARD.
Applies a slope to the measurement. The SLOPE is used for two-point calibrations along with the
STANDARD above. If you assigned the min value of your process to the STANDARD, then assign the
max value to the SLOPE. Also, assign the min value to the SLOPE. The slope and standard values
must be at least 0.1 units apart.
Resets Standard and Slope calibration to factory settings. After pressing
►
, select YES/NO.
Enter date of calibration (MM-DD-YYYY) and initials of calibrator (XX).
CH2 4-20mA INPUT
HOLD OUTPUTS
OFF
CH2 4-20mA INPUT
C
SET STANDARD
N-
CH2 4-20mA INPUT
SET SLOPE
L
CH2 4-20mA INPUT
RESET CAL
CH2 4-20mA INPUT
12-31-2015 XX
LAST CAL
F