63
GF 9950-10 Six Channel Transmitter
Common Menus
(ALL) Enter 17-character string, if desired.
Default = MEMO
Select which MODULE port the Modbus Module is installed into, MOD1, MOD 2 or NONE
Default = NONE.
Press
►
to change the settings of the Modbus Module.
Screen available when Modbus module is enabled.
Refer to Modbus Communication Settings Menus, page 78
Setting Modbus Remote update to YES allows remote Modbus device to change the settings on the 9950.
Setting Modbus Remote Update to NO prevents remote devices from make any changes to the 9950.
Screen available when the Modbus module is enabled.
Remote device will still be able to read all of the Modbus parameters.
Master Reset - Sets the 9950 back to Factory settings.
Displays Transmitter Generation Version.
QR code for user manual.
OPTION Menu
9950
SEC
GENERATION 3
USER MANUAL
SEC
100.00
View Measurement 1 displays the primary value with the secondary value below.
This is the normal display and does not time out.
View Measurement 2 displays the primary value and the channel name. This screen does not time out.
Parameter speci
fi
c screen.
Flow totalizer, pH raw mV, ORP, pH Impedance, pH/ORP Sensor Data, raw mV, 4 - 20 mA input, conductivity,
DO cap expiration date.
Displays the internal 4 to 20 mA LOOP output for each channel assigned primary and secondary sources.
(3.6, 22.00 are error output values).
Function values are stated to the right of the function number. Select a derived measurement function,
up to four functions available. (SUM, DIFFERENCE, RATIO, % PASSAGE, % REJECT, % RECOVERY A,
% RECOVERY B, % RECOVERY C) (Refer to page 20 for further details)
Displays the Module 4 to 20 mA LOOP output for each channel assigned primary and secondary sources.
(3.6, 22.00 are error output values).
Measurement View Mode Screens are depicted in the Sensor Speci
fi
c Menus.
Below are the screens that all parameters share in common.
Func 1
Func 2
Func 3
Func 4
50.00
100.00
2.00
0.00
CH 1 TOTALIZER
R 40560.0 ->
P 40560.0
LITERS
CH1
50.30
40560.0
987.9
65.5
CH2
GPM
R
GPM
R
0.00
0.00
100.00
100.00
VIEW Mode
LOOP 1
LOOP 2
12.00
4.00
INTERNAL LOOPS
MODULE LOOPS
MOD1 A
MOD1 B
18.00
12.00
MOD2 A
MOD2 B
8.00
4.00
MEMO
SEC
MEMO
MODBUS
NONE
MODULE
MODBUS
SETTINGS ->
COMMUNICATION
MODBUS
NO
REMOTE UPDATE
RESET TO
NO
FACTORY
CH1
50.30
FLOW
CH2
987.9
FLOW
GPM
GPM
100.00
0.00
0.00
100.00