17
GF 9950-10 Six Channel Transmitter
Example: Set a relay R1 to
turn on at a low setpoint of
5.5 gpm with a time delay of
15 seconds and turn off at
8.0 gpm.
Remember,
SET LOW + hysteresis = OFF
Relay 1 Source = CH1 Primary
Relay 1 Mode = Low
R1 Set Low = 5.5
R1 Hysteresis = 2.50
R1 on delay = 15.0 sec
Fail-Safe Behavior
No matter the setting, the Open Collector output turns off if the 9950 looses power. This must be taken into account when
evaluating system failure consequences. If the system layout requires a "closed" or "on" condition for the output in case of power
loss, a mechanical dry-contact relay (NC contacts) must be used instead of the Open Collector (R1) output.
Set your relay functions to your own application requirements.
1.
Press and hold ENTER for 3 seconds
2.
Go to the Relay Menu by pressing
▼
▼
▼
then ENTER
3. Press
the
►
to select desired source. You will be asked to enter a code or
password. Select source and press ENTER to con
fi
rm
4. Press
▼
to enter the relay
MODE
selection screen
5. Press
►
and then
▼
to select
R1 MODE LOW
. Press ENTER to confirm
6. Press
▼
to
R1 SET LOW
. Press
►
to enter GPM value of 5.5
7. Use
the
▲
and
▼
to change Set Point.
Press ENTER to save
8. Scroll
▼
to the
R1 HYSTERESIS
menu
9. Press
►
to edit
10. Set the hysteresis for this relay. Set the value to
2.5 gpm
11. Press
ENTER
12. Scroll
down
▼
to the
R1 ON DELAY
menu
13. Press
►
to edit
14. Set the turn-on delay in seconds for the relay:
15.0
15. Press ENTER Then
16. Exit to View Mode
●
Relay function can be tested in the RELAY menu
Once a setting is saved it becomes immediately active.
Relay Functions
When connecting a non-GF sensor to the 9950, the sensor’s 4 to 20 mA signal must be
converted to Digital (S
3
L). The 8058 i-Go Signal Converter accepts any 4 to 20 mA signal
and converts it into Digital (S
3
L).
1. Wire the 8058 between the 4 to 20 mA loop source and the 9950 Digital (S
3
L) input
terminals.
2. In the 9950 INPUT menu, sensor TYPE screen, select the '4 to 20 INPUT' sensor
(Refer to System Setup Menu, page 11).
8058-1
Input
4-to-20 mA
Output
S
3 L
Signet 8058 i-Go™
4-20 mA to S
3
L Converter
+GF+
4-20 mA input
S
3
L Output
Black
Red
Shield
9950 S
3
L Inputs
+V
FREQ
DATA
GND
+V
FREQ
DATA
GND
Loop1+
Loop1–
Loop2+
Loop2–
PWR+
PWR–
CH2
CH1
DC POWER
+V
FREQ
DATA
GND
X
No connection
White
8058-2
8058-2
close-up
4-20 mA
Input
N/C 3
Loop1 - 2
Loop1 + 1
+GF+
S L
Output
3
7 +5VDC
8 S L
9 GND
3
8058 i-Go™
4-20mA
to S
3
L
Converter
3-8058.610D
35VD
C MAX
N/C 6
Loop2 - 5
Loop2+ 4
3 2
1
6 5
4
7 8
9
Loo
p1
PW
R
+GF
+
N/C
S L
DA
TA
3
Loo
p2
PWR
Sign
et 805
8
7 8 9
N/C
S L
DATA
3
Black
Red
White
9950 S
3
L Inputs
+V
FREQ
DATA
GND
+V
FREQ
DATA
GND
Loop1+
Loop1–
Loop2+
Loop2–
PWR+
PWR–
CH2
CH1
DC POWER
+V
FREQ
DATA
GND
X
No connection
8058-1
Signal Type: 4 to 20 mA