36
GF 9950-10 Six Channel Transmitter
Press ENTER to start assigning sensors to each channel.
Use the
▲
and
▼
arrow to go to any of the six channels directly.
NOTE: Display only available when the 9950 is in FACTORY mode.
Press the
►
arrow, use the
▲
and
▼
arrow to select which TYPE of sensor will be assigned to the
channel(s) (1-6).
Choose 4-20mA, press ENTER to save sensor type.
Press the
►
arrow, using the
▲
or
▼
to select the input source to the channel.
Sources list will only contain 4-20mA sensors or modules.
To change sensor selection after it's been assigned, change the source to NONE, then the sensors
can be reassigned.
English, French, German, and Spanish Only. If desired, a custom name can be entered.
Enter 17-character string.
Default = 4-20 mA
Units are selectable from a list, IF the user selects CUST, the CUSTOM UNITS screen is displayed
following this SENSOR UNITS screen. Custom units are only available for English, German, French and
Spanish languages. Enter up to 4 characters describing unit of measure.
Default = UNIT
Measurement value of your sensor when its output is 4.00 mA.
4 to 20 mA Setup Checklist
1. Make sure 4 to 20 mA INPUT sensor type is selected.
(Refer to System Setup Menu, page 11)
2. Set 4 mA value. (refer to your 3rd-party sensor manual)
3. Set 20 mA value. (refer to your 3rd-party sensor manual)
4. If LOOP is used, set the minimum and maximum 4 to 20 mA setpoints.
5. Set Last Cal Date and initials.
6. If applicable, set up relay functions for your application.
Displays the input value. This is the
normal display and does not time out.
View Measurement 3 displays the primary value and the channel name. This screen does not time out.
4 to 20 mA input live readout.
4 to 20 mA
CH1
50.0
CUSTOM LABEL
CH2
CUSTOM LABEL
UNIT
UNIT
53.0
0.0
5.0
0.0
5.0
CH1
50.0
4-20 mA INPUT
CH2
4-20 mA INPUT
UNIT
UNIT
32.0
5.0
0.0
5.0
0.0
VIEW Mode Menu
4-20 mA INPUT
CH2 4.50
mA
h
CH1 12.00
mA
h
INPUT Menu
CH 2 4-20 mA
NONE
SOURCE
SETUP
CHANNEL 2
CH 2 FACTORY
FACTORY
TYPE
ENTER
CHANNEL 2
4-20mA INPUT
AV
NAME
FE°°
CH2 4-20mA INPUT
SENSOR UNITS
UNIT
CH2 4-20 mA INPUT
4 mA VALUE
0.00