GE Multilin
T60 Transformer Protection System
5-333
5 SETTINGS
5.9 TRANSDUCER INPUTS AND OUTPUTS
5
•
If the
RRTD 1 APPLICATION
setting is “Group 1” or “Group 2”, then a value of “Other” is written to the RRTD device.
An RRTD actual value of –43°C implies that the
RRTD 1 FUNCTION
setting is “Enabled” but the corresponding
RRTD 1 APPLI-
CATION
setting is
“
None
”
.
If the RRTD communication link with the T60 is broken, then the last temperature actual values are retained until the RRTD
communication failure is detected. When this occurs, a RRTD COMM FAILURE self-test alarm and target message is gen-
erated, and an event is logged in the event recorder and the temperature actual values reset to 0. When the link is re-estab-
lished, the
RRTD 1 APPLICATION
and
RRTD 1 TYPE
settings are read from the RRTD to re-synchronize the device.
•
RRTD 1 FUNCTION
: This setting enables and disables the remote RTD. If set to “Disabled”, no actual value is created
for the remote RTD.
•
RRTD 1 ID
: This setting is used to assign alphanumeric ID is assigned to the remote RTD. This ID will be included in
the remote RTD actual values. It is also used to reference the remote RTD input to features using the remote RTD.
•
RRTD 1 TYPE
: This setting specifies the remote RTD type. Four different RTD types are available: 100
Ω
Nickel, 10
Ω
Copper, 100
Ω
Platinum, and 120
Ω
Nickel.
The RRTD converts resistance to temperature as per the values in the following table. The T60 reads the RTD temper-
atures from the RRTD once every five seconds and applies protection accordingly. The RRTDs can be used to provide
RTD bias in the existing thermal model.
An RRTD open condition is detected when actual RRTD resistance is greater than 1000 ohms and RRTD open is dis-
played as “250°C” in the T60.
Table 5–39: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
RESISTANCE (IN OHMS)
°C
°F
100 OHM PT
(DIN 43760)
120 OHM NI
100 OHM NI
10 OHM CU
–40
–40
84.27
92.76
79.13
7.49
–30
–22
88.22
99.41
84.15
7.88
–20
–4
92.16
106.15
89.23
8.26
–10
14
96.09
113
94.58
8.65
0
32
100
120
100
9.04
10
50
103.9
127.17
105.6
9.42
20
68
107.79
134.52
111.2
9.81
30
86
111.67
142.06
117.1
10.19
40
104
115.54
149.79
123
10.58
50
122
119.39
157.74
129.1
10.97
60
140
123.24
165.9
135.3
11.35
70
158
127.07
174.25
141.7
11.74
80
176
130.89
182.84
148.3
12.12
90
194
134.7
191.64
154.9
12.51
100
212
138.5
200.64
161.8
12.9
110
230
142.29
209.85
168.8
13.28
120
248
146.06
219.29
176
13.67
130
266
149.82
228.96
183.3
14.06
140
284
153.58
238.85
190.9
14.44
150
302
157.32
248.95
198.7
14.83
160
320
161.04
259.3
206.6
15.22
170
338
164.76
269.91
214.8
15.61
180
356
168.47
280.77
223.2
16
190
374
172.46
291.96
231.6
16.39
200
392
175.84
303.46
240
16.78
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...