5-190
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–77: PHASE DISTANCE ZONE 1 OP SCHEME
Figure 5–78: PHASE DISTANCE ZONE 2 OP SCHEME
For phase distance zone 2, there is a provision to start the zone timer with other distance zones or loop the pickup
flag to avoid prolonging phase distance zone 2 operation when the fault evolves from one type to another or
migrates from the initial zone to zone 2. Desired zones in the trip output function should be assigned to accomplish
this functionality.
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1.
OR
OR
OR
OR
AND
AND
AND
AND
AND
AND
837017A8.CDR
FLEXLOGIC OPERAND
PH DIST Z1 PKP AB
PH DIST Z1 SUPN IAB
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
OPEN POLE OP **
FLEXLOGIC OPERANDS
SETTING
PH DIST Z1 DELAY
T
PKP
0
T
PKP
0
T
PKP
0
FLEXLOGIC OPERAND
PH DIST Z1 PKP BC
FLEXLOGIC OPERAND
PH DIST Z1 PKP CA
PH DIST Z1 OP AB
PH DIST Z1 OP BC
PH DIST Z1 OP CA
FLEXLOGIC OPERANDS
PH DIST Z1 OP
FLEXLOGIC OPERANDS
OR
AND
OR
837036A1.CDR
from the open pole element (D60, L60, and L90 only)
FLEXLOGIC OPERAND
OPEN POLE OP
FLEXLOGIC OPERAND
PH DIST Z2 PKP AB
FLEXLOGIC OPERAND
PH DIST Z2 PKP BC
FLEXLOGIC OPERAND
PH DIST Z2 PKP CA
TIMER
0 ms
20 ms
TIMER
0 ms
20 ms
TIMER
0 ms
20 ms
SETTING
PH DIST Z2 DELAY
T
PKP
0
SETTING
PH DIST Z2 DELAY
T
PKP
0
SETTING
PH DIST Z2 DELAY
T
PKP
0
FLEXLOGIC OPERAND
PH DIST Z2 OP AB
FLEXLOGIC OPERAND
PH DIST Z2 OP BC
FLEXLOGIC OPERAND
PH DIST Z2 OP CA
FLEXLOGIC OPERAND
PH DIST Z2 OP
FLEXLOGIC OPERAND
TRIP Z2 PH TMR INIT
OR
OR
OR
AND
OR
AND
OR
AND
AND
AND
from the trip output element
NOTE
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...