B-20
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
2308
Transformer Differential 5th Harm Iad Angle
-359.9 to 0
degrees
0.1
F002
0
2309
Transformer Differential Phasor Ibd Magnitude
0 to 30
pu
0.001
F001
0
230A
Transformer Differential Phasor Ibd Angle
-359.9 to 0
degrees
0.1
F002
0
230B
Transformer Restraint Phasor Ibr Magnitude
0 to 30
pu
0.001
F001
0
230C
Transformer Restraint Phasor Ibr Angle
-359.9 to 0
degrees
0.1
F002
0
230D
Transformer Differential 2nd Harm Ibd Magnitude
0 to 999.9
% fo
0.1
F001
0
230E
Transformer Differential 2nd Harm Ibd Angle
-359.9 to 0
degrees
0.1
F002
0
230F
Transformer Differential 5th Harm Ibd Magnitude
0 to 999.9
% fo
0.1
F001
0
2310
Transformer Differential 5th Harm Ibd Angle
-359.9 to 0
degrees
0.1
F002
0
2311
Transformer Differential Phasor Icd Magnitude
0 to 30
pu
0.001
F001
0
2312
Transformer Differential Phasor Icd Angle
-359.9 to 0
degrees
0.1
F002
0
2313
Transformer Restraint Phasor Icr Magnitude
0 to 30
pu
0.001
F001
0
2314
Transformer Restraint Phasor Icr Angle
-359.9 to 0
degrees
0.1
F002
0
2315
Transformer Differential 2nd Harm Icd Magnitude
0 to 999.9
% fo
0.1
F001
0
2316
Transformer Differential 2nd Harm Icd Angle
-359.9 to 0
degrees
0.1
F002
0
2317
Transformer Differential 5th Harm Icd Magnitude
0 to 999.9
% fo
0.1
F001
0
2318
Transformer Differential 5th Harm Icd Angle
-359.9 to 0
degrees
0.1
F002
0
Transformer Thermal Inputs Actual Values (Read Only)
2330
Transformer Top Oil Temperature
0 to 300
°C
1
F002
0
2331
Transformer Hottest Spot Temperature
0 to 300
°C
1
F002
0
2332
Transformer Aging Factor
0 to 6553.5
PU
0.1
F001
0
2333
Transformer Daily Loss Of Life
0 to 500000
Hours
1
F060
0
Transformer Thermal Inputs Actual Values (Read Only Non-Volatile)
2335
Transformer Loss of Life
0 to 500000
Hours
1
F060
0
Synchrocheck Actual Values (Read Only) (4 modules)
2400
Synchrocheck 1 Delta Voltage
-1000000000000 to
1000000000000
V
1
F060
0
2402
Synchrocheck 1 Delta Frequency
0 to 655.35
Hz
0.01
F001
0
2403
Synchrocheck 1 Delta Phase
0 to 180 (not 0 to 359.9)
degrees
0.1
F001
0
2404
...Repeated for Synchrocheck 2
2408
...Repeated for Synchrocheck 3
240C
...Repeated for Synchrocheck 4
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
0 to 7
---
1
F244
6 (H1a)
2461
Field Raw Data Freeze
0 to 1
---
1
F102
0 (Disabled)
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2540
Remote Double-point Status Input 1 Device
1 to 32
---
1
F001
1
2541
Remote Double-point Status Input 1 Item
0 to 64
---
1
F606
0 (None)
2542
Remote Double-point Status Input 1 Name
1 to 64
---
1
F205
"RemDPS Ip 1"
2548
Remote Double-point Status Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
2549
... Repeated for Remote Double-point Status Input 2
2552
... Repeated for Remote Double-point Status Input 3
255B
... Repeated for Remote Double-point Status Input 4
2564
... Repeated for Remote Double-point Status Input 5
Phasor Measurement Unit Actual Values (Read Only)
256D
PMU 1 Phase A Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
256F
PMU Unit 1 Phase A Voltage Angle
-180 to 180
°
0.01
F002
0
2570
PMU 1 Phase B Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2572
PMU 1 Phase B Voltage Angle
-180 to 180
°
0.01
F002
0
2573
PMU 1 Phase C Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2575
PMU 1 Phase C Voltage Angle
-180 to 180
°
0.01
F002
0
2576
PMU 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2578
PMU 1 Auxiliary Voltage Angle
-180 to 180
°
0.01
F002
0
2579
PMU 1 Positive Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...