GE Multilin
T60 Transformer Protection System
5-23
5 SETTINGS
5.2 PRODUCT SETUP
5
Role
— 16 bit unsigned, of type format F617
Activity Value
— 16 bit unsigned
The following events are recorded in the syslog.
Table 5–3: SYSTEM EVENTS RECORDED
ENUMERATION
ROLE
0
None
1
Administrator
2
Supervisor
3
Engineer
4
Operator
5
Factory
ENUMERATION
DESCRIPTION
1
Authentication Failed
2
User Lockout
3
FW Upgrade
4
FW Lock
5
Settings Lock
6
Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7
Clear Oscillography command
8
Clear Data Logger command (not applicable to all UR products)
9
Clear Demand Records command (not applicable to all UR products)
10
Clear Energy command (not applicable to all UR products)
11
Clear Unauthorized Access command
12
Clear Teleprotection Counters command (not applicable to all UR products)
13
Clear All Relay Records command
14
Role Log in
15
Role Log off
EVENT
SEVERITY
DESCRIPTION
FAILED_AUTH, ORIGIN,
TIMESTAMP
Warning (4)
A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
AUTH_LOCKOUT, ORIGIN,
TIMESTAMP
Error (3)
An authentication lockout has occurred because of too many failed
authentication attempts
FIRMWARE_UPGD, ORIGIN,
TIMESTAMP
Warning (4)
Indicates that a change of firmware has occurred
FIRMWARE_LOCK, ORIGIN,
TIMESTAMP
Critical (1)
An attempt was made to change firmware while the firmware lock was
enabled
SETTING_CHG, ORIGIN,
TIMESTAMP
Notice (5)
Indicates setting change(s)
SETTING_LOCK, ORIGIN,
TIMESTAMP
Critical (1)
An attempt was made to change settings while the settings lock was enabled
LOGIN, ORIGIN, TIMESTAMP
Warning (4)
Indicates when a certain role logged in
LOGOUT, ORIGIN, TIMESTAMP
Notice (5)
Indicates when a certain role logged out or timed out
CLEAR_OSCILLOGRAPHY
Notice (5)
Clear oscillography command was issued
CLEAR_DATA_LOGGER
Notice (5)
Clear data logger command was issued
CLEAR_DEMAND_RECS
Notice (5)
Clear demand records command was issued
CLEAR_ENERGY
Notice (5)
Clear energy command was issued
RESET_UNAUTH_ACCESS
Warning (4)
Reset Unauthorized access command was issued
CLEAR_TELEPROTECTION_CNT
Notice (5)
Clear teleprotection counters command was issued
CLEAR_ALL_RECS
Warning (4)
Clear all records command was issued
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...