GE Multilin
T60 Transformer Protection System
5-55
5 SETTINGS
5.2 PRODUCT SETUP
5
The breaker configuration settings are shown below. Changes to these values take effect when the UR is restarted:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
XCBR CONFIGURATION
The XCBR1 ST.LOC OPERAND setting is used to inhibit 61850 control commands to close or open breaker through UR
Breaker Control element. See the Breaker Control element logic diagram for more information.
The CLEAR XCBR1 OpCnt setting allows clearing the breaker operating counter. As breakers operate by opening and
closing, the XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation
can result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.
XCBR
CONFIGURATION
XCBR1 ST.LOC OPERAND
Off
Range: FlexLogic operand
↓
MESSAGE
XCBR6 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
CLEAR XCBR1 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XCBR6 OpCnt:
No
Range: No, Yes
MESSAGE
XCBR1 SYNCCHECK CLS:
Off
Range: FlexLogic operand
↓
MESSAGE
XCBR6 SYNCCHECK CLS:
Off
Range: FlexLogic operand
MESSAGE
XCBR1 INTERLOCK OPN:
Off
Range: FlexLogic operand
↓
MESSAGE
XCBR6 INTERLOCK OPN:
Off
Range: FlexLogic operand
MESSAGE
XCBR1 INTERLOCK CLS:
Off
Range: FlexLogic operand
↓
MESSAGE
XCBR6 INTERLOCK CLS:
Off
Range: FlexLogic operand
MESSAGE
XCBR1 Pos ctlModel:
2
Range: 0 to 4 (as per IEC 61850-7-3, ctlModel)
↓
MESSAGE
XCBR6 Pos ctlModel:
2
Range: 0 to 4 (as per IEC 61850-7-3, ctlModel)
MESSAGE
XCBR1 Pos
sboTimeout: 30 s
Range: 2 to 60 seconds
↓
MESSAGE
XCBR6 Pos
sboTimeout: 30 s
Range: 2 to 60 seconds
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...