GE Multilin
T60 Transformer Protection System
B-17
APPENDIX B
B.4 MEMORY MAPPING
B
1A11
Source 1 Phase BC or BA Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A13
Source 1 Phase CA or CB Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A15
Source 1 Phase AB or AC Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A17
Source 1 Phase AB or AC Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A18
Source 1 Phase BC or BA Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1A
Source 1 Phase BC or BA Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1B
Source 1 Phase CA or CB Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1D
Source 1 Phase CA or CB Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1E
Source 1 Auxiliary Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A20
Source 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A22
Source 1 Auxiliary Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A23
Source 1 Zero Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A25
Source 1 Zero Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A26
Source 1 Positive Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A28
Source 1 Positive Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A29
Source 1 Negative Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A2B
Source 1 Negative Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A2C
Reserved (20 items)
---
---
---
F001
0
1A40
...Repeated for Source 2
1A80
...Repeated for Source 3
1AC0
...Repeated for Source 4
1B00
...Repeated for Source 5
1B40
...Repeated for Source 6
Source Power (Read Only) (6 modules)
1C00
Source 1 Three Phase Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C02
Source 1 Phase A Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C04
Source 1 Phase B Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C06
Source 1 Phase C Real Power
-1000000000000 to
1000000000000
W
0.001
F060
0
1C08
Source 1 Three Phase Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C0A
Source 1 Phase A Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C0C
Source 1 Phase B Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C0E
Source 1 Phase C Reactive Power
-1000000000000 to
1000000000000
var
0.001
F060
0
1C10
Source 1 Three Phase Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C12
Source 1 Phase A Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C14
Source 1 Phase B Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C16
Source 1 Phase C Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C18
Source 1 Three Phase Power Factor
-0.999 to 1
---
0.001
F013
0
1C19
Source 1 Phase A Power Factor
-0.999 to 1
---
0.001
F013
0
1C1A
Source 1 Phase B Power Factor
-0.999 to 1
---
0.001
F013
0
1C1B
Source 1 Phase C Power Factor
-0.999 to 1
---
0.001
F013
0
1C1C
Reserved (4 items)
---
---
---
F001
0
1C20
...Repeated for Source 2
1C40
...Repeated for Source 3
1C60
...Repeated for Source 4
1C80
...Repeated for Source 5
1CA0
...Repeated for Source 6
Table B–10: MODBUS MEMORY MAP (Sheet 9 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...