GE Multilin
T60 Transformer Protection System
B-27
APPENDIX B
B.4 MEMORY MAPPING
B
3897
Remote Ground CT 1 Primary
1 to 65000
---
1
F001
1
3898
Remote Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
3899
Remote Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
389A
Remote Phase VT 1 Secondary
25 to 240
---
0.1
F001
664
389B
Remote Phase VT 1 Ratio
1 to 24000
---
1
F060
1
389D
Remote Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
389E
Remote Auxiliary VT 1 Secondary
25 to 240
---
0.1
F001
664
389F
Remote Auxiliary VT 1 Ratio
1 to 24000
---
1
F060
1
38A1
...Repeated for Field Unit 2
38B2
...Repeated for Field Unit 3
38C3
...Repeated for Field Unit 4
38D4
...Repeated for Field Unit 5
38E5
...Repeated for Field Unit 6
Field Unit Contact Inputs (Read/Write Setting) (40 modules)
3900
Field Contact Input 1 ID
---
---
---
F205
"FCI 1"
3906
Field Contact Input 1 Origin
0 to 8
---
1
F256
0 (None)
3907
Field Contact Input 1 Input
1 to 18
---
1
F001
1
3908
Field Contact Input 1 Failsafe Value
0 to 1
---
1
F108
0 (Off)
3909
Field Contact Input 1 Debounce Time
0 to 16
ms
0.5
F001
20
390A
Field Contact Input 1 Events
0 to 1
---
1
F102
1 (Enabled)
390B
...Repeated for Field Contact Input 2
3916
...Repeated for Field Contact Input 3
3921
...Repeated for Field Contact Input 4
392C
...Repeated for Field Contact Input 5
3937
...Repeated for Field Contact Input 6
3942
...Repeated for Field Contact Input 7
394D
...Repeated for Field Contact Input 8
3958
...Repeated for Field Contact Input9
3963
...Repeated for Field Contact Input 10
396E
...Repeated for Field Contact Input 11
3979
...Repeated for Field Contact Input 12
3984
...Repeated for Field Contact Input 13
398F
...Repeated for Field Contact Input 14
399A
...Repeated for Field Contact Input 15
39A5
...Repeated for Field Contact Input 16
39B0
...Repeated for Field Contact Input 17
39BB
...Repeated for Field Contact Input 18
39C6
...Repeated for Field Contact Input 19
39D1
...Repeated for Field Contact Input 20
39DC
...Repeated for Field Contact Input 21
39E7
...Repeated for Field Contact Input 22
39F2
...Repeated for Field Contact Input 23
39FD
...Repeated for Field Contact Input 24
3A08
...Repeated for Field Contact Input 25
3A13
...Repeated for Field Contact Input 26
3A1E
...Repeated for Field Contact Input 27
3A29
...Repeated for Field Contact Input 28
3A34
...Repeated for Field Contact Input 29
3A3F
...Repeated for Field Contact Input 30
3A4A
...Repeated for Field Contact Input 31
3A55
...Repeated for Field Contact Input 32
3A60
...Repeated for Field Contact Input 33
3A6B
...Repeated for Field Contact Input 34
3A76
...Repeated for Field Contact Input 35
Table B–10: MODBUS MEMORY MAP (Sheet 19 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...