5-38
T60 Transformer Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
j) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL
DNP PROTOCOL
DNP CHANNELS
Range: see sub-menu below
MESSAGE
DNP ADDRESS:
1
Range: 0 to 65519 in steps of 1
MESSAGE
DNP NETWORK
CLIENT ADDRESSES
Range: see sub-menu below
MESSAGE
DNP TCP/UDP PORT
NUMBER: 20000
Range: 0 to 65535 in steps of 1
MESSAGE
DNP UNSOL RESPONSE
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
DNP UNSOL RESPONSE
TIMEOUT: 5 s
Range: 0 to 60 s in steps of 1
MESSAGE
DNP UNSOL RESPONSE
MAX RETRIES: 10
Range: 1 to 255 in steps of 1
MESSAGE
DNP UNSOL RESPONSE
DEST ADDRESS: 1
Range: 0 to 65519 in steps of 1
MESSAGE
DNP CURRENT SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP VOLTAGE SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP POWER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP ENERGY SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP PF SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP OTHER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP CURRENT DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP VOLTAGE DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP POWER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP ENERGY DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP PF DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP OTHER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP TIME SYNC IIN
PERIOD: 1440 min
Range: 1 to 10080 min. in steps of 1
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...