5-184
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8:
Theory of operation
.
Although all zones can be used as either instantaneous elements (pickup [
PKP
] and dropout [
DPO
] FlexLogic operands) or
time-delayed elements (operate [
OP
] FlexLogic operands), only zone 1 is intended for the instantaneous under-reaching
tripping mode.
Ensure that the Phase VT Secondary Voltage setting (see the
SETTINGS
SYSTEM SETUP
AC
INPUTS
VOLTAGE BANK
menu) is set correctly to prevent improper operation of associated mem-
ory action.
•
PHS DIST Z1 DIR:
All phase distance zones are reversible. The forward direction is defined by the
PHS DIST Z1 RCA
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the
PHS DIST Z1 REACH
and
PHS DIST Z1 RCA
settings, and the reverse reach imped-
ance defined by
PHS DIST Z1 REV REACH
and
PHS DIST Z1 REV REACH RCA
as illustrated below.
•
PHS DIST Z1 SHAPE:
This setting selects the shape of the phase distance function between the mho and quadrilat-
eral characteristics. The selection is available on a per-zone basis. The two characteristics and their possible varia-
tions are shown in the following figures.
Figure 5–70: DIRECTIONAL MHO DISTANCE CHARACTERISTIC
NOTICE
837720A1.CDR
X
R
R
EAC
H
RCA
DIR RCA
DIR COMP LIMIT
DIR COMP LIMIT
COMP LIMIT
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...