GE Multilin
T60 Transformer Protection System
F-7
APPENDIX F
F.1 DEVICE PROFILE DOCUMENT
F
34
cont’d
2
32-bit Analog Input Reporting Deadband
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
2
(write)
00, 01
(start-stop)
07, 08
(limited quantity)
17, 28
(index)
3
Short floating point Analog Input Reporting
Deadband
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
50
1
Time and Date
(default – see Note 1)
1
(read)
2
(write)
00, 01
(start-stop)
06
(no range, or all)
07
(limited qty=1)
08
(limited quantity)
17, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index)
(see Note 2)
52
2
Time Delay Fine
129
(response)
07
(limited quantity)
(quantity = 1)
60
0
Class 0, 1, 2, and 3 Data
1
(read)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
1
Class 0 Data
1
(read)
22
(assign class)
06
(no range, or all)
2
Class 1 Data
1
(read)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
07, 08
(limited quantity)
3
Class 2 Data
4
Class 3 Data
70
0
File event - any variation
1
(read)
06
(no range, or all)
07, 08
(limited quantity)
22
(assign class)
06
(no range, or all)
2
File authentication
29
(authenticate)
5b
(free format)
129
(response)
5b
(free format)
3
File command
25
(open)
27
(delete)
5b
(free format)
4
File command status
26
(close)
30
(abort)
5b
(free format)
129
(response)
130
(unsol. resp.)
5b
(free format)
5
File transfer
1
(read)
2
(write)
5b
(free format)
129
(response)
130
(unsol. resp.)
5b
(free format)
6
File transfer status
129
(response)
130
(unsol. resp.)
5b
(free format)
7
File descriptor
28
(get file info.)
5b
(free format)
129
(response)
130
(unsol. resp.)
5b
(free format)
80
1
Internal Indications
1
(read)
00, 01
(start-stop)
(index =7)
129
(response)
00, 01
(start-stop)
2
(write)
(see Note 3)
00
(start-stop)
(index =7)
---
No Object (function code only)
see Note 3
13
(cold restart)
---
No Object (function code only)
14
(warm restart)
---
No Object (function code only)
23
(delay meas.)
Table F–2: IMPLEMENTATION TABLE (Sheet 4 of 4)
OBJECT
REQUEST
RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION
FUNCTION
CODES (DEC)
QUALIFIER
CODES (HEX)
FUNCTION
CODES (DEC)
QUALIFIER
CODES (HEX)
Note 1:
A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. See the
Communications
section in Chapter 5 for
details. This optimizes the class 0 poll data size.
Note 2:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3:
Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted.
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...