5-106
T60 Transformer Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
Figure 5–25: DISTURBANCE DETECTOR LOGIC DIAGRAM
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting (
PROD-
UCT SETUP
DISPLAY PROPERTIES
CURRENT CUT-OFF LEVEL
) controls the sensitivity of the disturbance detector
accordingly.
EXAMPLE USE OF SOURCES:
An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration:
This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
INCREASING SLOT POSITION LETTER
-->
CT/VT MODULE 1
CT/VT MODULE 2
CT/VT MODULE 3
CTs
VTs
not applicable
827092A3.CDR
SOURCE 1
CURRENT PHASOR
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
SOURCE 2
CURRENT PHASOR
SOURCE 6
CURRENT PHASOR
ACTUAL
SETTING
SETTING
SETTING
ACTUAL
ACTUAL
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
I
_1
I
_1
I
_1
SRC 1 50DD OP
SRC 2 50DD OP
SRC 6 50DD OP
I
_2
I
_2
I
_2
I
_0
I
_0
I
_0
OR
OR
OR
Where ’ is 2 cycles old
I
Where ’ is 2 cycles old
I
Where ’ is 2 cycles old
I
I
I
_1 - _1’ >2*CUT-OFF
I
I
_1 - _1’ >2*CUT-OFF
I
I
_1 - _1’ >2*CUT-OFF
I
I
_2 - _2’ >2*CUT-OFF
I
I
_2 - _2’ >2*CUT-OFF
I
I
_2 - _2’ >2*CUT-OFF
I
I
_0 - _0’ >2*CUT-OFF
I
I
_0 - _0’ >2*CUT-OFF
I
I
_0 - _0’ >2*CUT-OFF
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...