5-326
T60 Transformer Protection System
GE Multilin
5.8 INPUTS AND OUTPUTS
5 SETTINGS
5
Figure 5–167: TELEPROTECTION INPUT/OUTPUT PROCESSING
5.8.12 IEC 61850 GOOSE ANALOGS
PATH: SETTINGS
INPUTS/OUTPUTS
IEC 61850 GOOSE ANALOGS
GOOSE ANALOG INPUT 1(32)
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
•
ANALOG 1 DEFAULT
: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the
ANALOG 1 DEFAULT MODE
is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floating
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
•
ANALOG 1 DEFAULT MODE
: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE analog input is defined by the
ANALOG 1 DEFAULT
setting.
•
GOOSE ANALOG 1 UNITS
: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user to
configure GOOSE Analog, so that it can be used in a FlexElement.
GOOSE ANALOG
INPUT 1
ANALOG 1
DEFAULT:
1000.000
Range: –1000000.000 to 1000000.000 in steps of 0.001
MESSAGE
ANALOG 1
DEFAULT
MODE: Default Value
Range: Default Value, Last Known
MESSAGE
GOOSE ANALOG 1
UNITS:
Range: up to 4 alphanumeric characters
MESSAGE
GOOSE ANALOG 1 PU:
1.000
Range: 0.000 to 1000000000.000 in steps of 0.001
842750A2.CDR
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16)
TELEPROT INPUT 1-1
DEFAULT:
(same for 1-2...1-16)
Off (Flexlogic Operand)
TELEPRO INPUT 1-1 On
(same for 1-2...1-16)
UR-1
(Teleprotection I/O Enabled)
Communication channel #1
On
Off
ACTUAL VALUES
CHANNEL 1 STATUS:
Fail
OK
OR
SETTING
TELEPROT OUTPUT 1-1:
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
FLEXLOGIC OPERAND
TELEPRO INPUT 1-1 On
TELEPRO INPUT 2-1 On
(same for 1-2...1-16)
UR-2
SETTING
SETTING
TELEPROT INPUT 1-1
TELEPROT INPUT 2-1
DEFAULT:
(same for 1-2...1-16)
On
Off
Fail
OK
OR
ACTUAL VALUES
ACTUAL VALUES
CHANNEL 1 STATUS:
(On 3-terminal system or 2-terminal
with redundant channel)
Communication channel #2
On
Off
ACTUAL VALUES
CHANNEL 2 STATUS:
Fail
OK
OR
SETTING
(same for 2-2...2-16)
Off (Flexlogic Operand)
FLEXLOGIC OPERAND
(same for 2-2...2-16)
DEFAULT:
(same for 2-2...2-16)
On
Off
Fail
OK
OR
CHANNEL 2 STATUS:
UR-2 or UR-3
SETTING
SETTING
FLEXLOGIC OPERAND
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16)
TELEPROT INPUT 2-1
DEFAULT:
(same for 1-2...1-16)
Off (Flexlogic Operand)
TELEPRO INPUT 2-1 On
(same for 1-2...1-16)
SETTING
SETTING
FLEXLOGIC OPERAND
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...