GE Multilin
T60 Transformer Protection System
5-139
5 SETTINGS
5.4 SYSTEM SETUP
5
b) BASIC CONFIGURATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
BASIC CONFIGURATION
PMU1
PMU 1 BASIC
CONFIGURATION
PMU 1
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 IDCODE:
1
Range: 1 to 65534 in steps of 1
MESSAGE
PMU 1 STN:
GE-UR-PMU
Range: 32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
MESSAGE
PMU 1 SIGNAL SOURCE:
SRC 1
Range: Available signal sources
MESSAGE
PMU 1 CLASS:
CLASS M
Range: None, CLASS M, CLASS P
MESSAGE
PMU 1 FORMAT:
Integer
Range: Integer, Floating-point
MESSAGE
PMU 1 STYLE:
Polar
Range: Polar, Rectangular
MESSAGE
PMU 1 RATE:
10/sec
Range:1/sec, 2/sec, 4/sec, 5/sec, 10/sec, 12/sec, 15/sec,
20/sec, 25/sec, 30/sec, 50/sec, 60/sec, 100/sec, 120/sec
MESSAGE
PMU 1 PHS-1:
Off
Range: Available synchrophasor values
↓
MESSAGE
PMU 1 PHS-14:
Off
Range: Available synchrophasor values
MESSAGE
PMU 1 PHS-1
NAME: GE-UR-PMU-PHS-1
Range: 16 -character ASCII string
↓
MESSAGE
PMU 1 PHS-14:
NAME: GE-UR-PMU-PHS-14
Range: 16 -character ASCII string
MESSAGE
PMU 1 A-CH-1:
Off
Range: Available FlexAnalog values
↓
MESSAGE
PMU 1 A-CH-16 (16):
Off
Range: Available FlexAnalog values
MESSAGE
PMU 1 A-CH-1:
NAME: AnalogChannel1
Range: 16 -character ASCII string
↓
MESSAGE
PMU 1 A-CH-16 (16):
NAME: AnalogChannel16
Range: 16 -character ASCII string
MESSAGE
PMU 1 D-CH-1:
Off
Range: Available FlexLogic operands
↓
MESSAGE
PMU 1 D-CH-16:
Off
Range: FlexLogic operand
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...