5-26
T60 Transformer Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma-
ble pushbuttons to clear specific records are typical applications for these commands. Since the T60 responds to rising
edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, the following settings should be applied.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
SETTINGS
PRODUCT SETUP
CLEAR RELAY RECORDS
menu:
CLEAR DEMAND:
“
PUSHBUTTON 1 ON
”
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETTINGS
PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION:
“Self-reset”
PUSHBTN 1 DROP-OUT TIME:
“0.20 s”
MESSAGE
CLEAR DEMAND:
Off
Range: FlexLogic operand
MESSAGE
CLEAR ENERGY:
Off
Range: FlexLogic operand
MESSAGE
RESET UNAUTH ACCESS:
Off
Range: FlexLogic operand
MESSAGE
CLEAR DIR I/O STATS:
Off
Range: FlexLogic operand.
Valid only for units with Direct I/O module.
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...