4-2
T60 Transformer Protection System
GE Multilin
4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
4 HUMAN INTERFACES
4
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address
IP Subnet Mask
IP Routing
When a settings file is loaded to a T60 that is in-service, the following sequence occurs:
1.
The T60 takes itself out of service.
2.
The T60 issues a
UNIT NOT PROGRAMMED
major self-test error.
3.
The T60 closes the critical fail contact.
c) CREATING AND EDITING FLEXLOGIC
You create or edit a FlexLogic equation in order to customize the relay. You can subsequently view the automatically gener-
ated logic diagram.
d) VIEWING ACTUAL VALUES
You can view real-time relay data such as input/output status and measured parameters.
e) VIEWING TRIGGERED EVENTS
While the interface is in either online or offline mode, you can view and analyze data generated by triggered specified
parameters, via one of the following:
•
Event recorder
The event recorder captures contextual data associated with the last 1024 events, listed in chronological order from
most recent to oldest.
•
Oscillography
The oscillography waveform traces and digital states are used to provide a visual display of power system and relay
operation data captured during specific triggered events.
f) FILE SUPPORT
•
Execution:
Any EnerVista UR Setup file that is opened launches the application or provides focus to the already
opened application. If the file was a settings file (has a
URS
extension) that had been removed from the Settings List
tree menu, it is added back to the Settings List tree menu.
•
Drag and Drop:
The Site List and Settings List control bar windows are each mutually a drag source and a drop target
for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any
Windows Explorer directory folder are each mutually a file drag source and drop target.
New files that are dropped into the Settings List window are added to the tree, which is automatically sorted alphabeti-
cally with respect to settings file names. Files or individual menu items that are dropped in the selected device menu in
the Site List window are automatically sent to the online communicating device.
g) FIRMWARE UPGRADES
The firmware of a T60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-
ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
If you are upgrading from version 7.0 or 7.1 to 7.2 or later, some CPU modules require a new boot version. Update this first
in EnerVista under
Maintenance > Update Firmware
.
Before backing up settings and upgrading, set the
Settings > Product Setup > Security > Dual Permission Security
Access > Remote Setting Authorized
and
Local Setting Authorized
settings to "ON." Otherwise, the upgrade is blocked
and results in an "Unable to put relay in flash mode" message.
If using CyberSentry security, also ensure that the relay and firmware are not locked under the
Settings > Product Setup
> Security > Supervisory
settings. A Supervisor role is required for these settings.
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...