GE Multilin
T60 Transformer Protection System
5-67
5 SETTINGS
5.2 PRODUCT SETUP
5
offset possibly greater than 10 µs from the international time standard, the CLOCK UNSYNCHRONIZED FlexLogic oper-
and is activated.
The
SYNCHRONIZING SOURCE
setting displays when the relay includes the IEEE 1588 software option. The setting config-
ures the priority sequence of the time synchronization source, to determine which of the available external time sources to
use for time synchronization. A setting of None causes the RTC and the synchrophasor clock to free-run until the clock is
changed from the front panel or from communications protocols. A setting of PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/SNTP,
or PP/PTP/IRIG-B/SNTP causes the relay to track the first source named that is enabled and operational, or free-run if
none of these are available. Here, PP means a time source that is strictly compliant with PP, and PTP means a time source
that is not strictly compliant with PP. When a time source fails or recovers, the relay automatically transfers synchronization
as required by this setting.
When the relay does not have the IEEE 1588 software option and this setting does not display, it uses IRIG-B when
enabled and operational, then failing that SNTP when configured and operational, and otherwise it free-runs unless the
clock is changed from the front panel or from communications protocols.
Whenever a time synchronization message is received through any of the active protocols, the UR clock updates. However,
given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low accuracy time synchronization methods, avoid
their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP, are active in the system.
See the
COMMANDS
SET DATE AND TIME
menu section of this manual to manually set the RTC.
The
REAL TIME CLOCK EVENTS
setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment. A Date/Time Changed event is generated when:
•
The real time clock changed from SNTP/PTP/IRIG-B and the time difference is more than one second
•
The real time clock changed from the front panel or via Modbus register. The relay always generates this event regard-
less of the time difference.
•
The Daylight Saving Time (DST) setting gets enabled and the current relay time is already in the DST zone
•
The real time clock enters or leaves DST
To enable IRIG-B synchronization, the input
IRIG-B SIGNAL TYPE
must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use
the following sections.
b) PRECISION TIME PROTOCOL (1588)
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
PRECISION TIME PROTOCOL (1588)
PRECISION TIME
PROTOCOL (1588)
STRICT POWER PROFILE:
Disabled
Range: Enabled, Disabled
MESSAGE
PTP DOMAIN NUMBER
0
Range: 0 to 255
MESSAGE
PTP VLAN PRIORITY
4
Range: 0 to 7
MESSAGE
PTP VLAN ID
0
Range: 0 to 4095
MESSAGE
PTP PORT 1
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...