GE Multilin
T60 Transformer Protection System
5-221
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Figure 5–103: AGING FACTOR LOGIC
f) LOSS OF LIFE
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
TRANSFORMER
LOSS OF LIFE
The Loss of Life element detects the accumulated total consumed transformer life. This element can be set to issue an
alarm or trip when the actual accumulated transformer life becomes larger than the user-specified loss of life pickup value.
For new transformers installations, the
XFMR INITIAL LOSS OF LIFE
setting should be “0”. For previously installed transform-
ers, the user should pre-determine the consumed transformer life in hours.
•
LOSS OF LIFE INITIAL VALUE
: Enter a setting for the consumed transformer life in hours. When the Loss of Life ele-
ment is enabled, the computed loss of life will be added to the initial loss of life.
•
LOSS OF LIFE PICKUP
: Enter the expended life, in hours, required for operation of the element. This setting should
be above the total transformer life set as a reference based on nominal loading conditions and a 30°C ambient temper-
ature, as outlined in the IEEE standards.
LOSS OF LIFE
LOSS OF LIFE
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LOSS OF LIFE INITIAL
VALUE: 0 hrs
Range: 0 to 500000 hrs. in steps of 1
MESSAGE
LOSS OF LIFE PICKUP:
180000 hrs
Range: 0 to 500000 hrs. in steps of 1
MESSAGE
LOSS OF LIFE BLOCK:
Off
Range: FlexLogic operand
MESSAGE
LOSS OF LIFE TARGET:
Self-Reset
Range: Self-reset, Latched, Disabled
SETTING
SETTING
ACTUAL VALUE
SETTINGS
FLEXLOGIC OPERANDS
AGING FACTOR
FUNCTION:
AGING FACTOR
BLOCK:
AGING FACTOR-FAA
FAA > PKP
t
PKP
RUN
AGING FACTOR
PICKUP DELAY:
AGING FACTOR
PICKUP:
AGING FACTOR OP
AGING FACTOR DPO
AGING FACTOR PKP
Enable=1
Off=0
828733A3.cdr
AND
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...