GE Multilin
T60 Transformer Protection System
5-153
5 SETTINGS
5.4 SYSTEM SETUP
5
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
90-5 AGGR 1 CONFIGURA-
TION
•
PMU AGGREGATOR1 PROTOCOL
: This setting selects if the IEEE C37.118 or IEC 61850-90-5 standard is used.
Because one protocol is supported at a time in a device, this setting applies to all PMU aggregators.
•
PMU AGGREGATOR1 IDCODE
: Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output
stream, this identifies the ID of the aggregator, which is only used if there is more than 1 PMU mapped into an aggre-
gator.
•
PMU AGGREGATOR1 PMU1
: If set to “Yes” aggregator 1 includes the PMU1 data set in the reporting data stream.
AGGREGATOR1 does not include PMU1 data set in the report if set to “No”.
Only PMUs with same reporting rate can be assigned to the same PMU AGGREGATOR.
C37.118 AGGREGATOR 1 CONFIGURATION
•
PMU AGGREGATOR1: TCP PORT
: This setting selects the TCP port number to be used by this aggregator for net-
work reporting. All ports, even those of unused aggregators, must be valid and unique to avoid port number collisions.
•
PMU AGGREGATOR1 UDP PORT
: This setting selects the UDP port number to be used by this aggregator for net-
work reporting. All ports, even those of unused aggregators, must be valid and unique to avoid port number collisions.
•
PMU AGGREGATOR1 PDC CONTROL
: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in the table. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is restarted. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
90-5 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
NAME:
Range: 56 character ASCII text
MESSAGE
PMU AGGREGATOR1:
PORT: 1
Range: 1, 2, 3
MESSAGE
PMU AGGREGATOR 1:
UDP PORT: 102
Range: 1 to 65534 in steps of 1
MESSAGE
PMU AGGREGATOR 1:
NUMBER OF ASDUs: 1
Range: 1 to 4
Table 5–17: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
ELEMENT:
Synchrophasor, phasor data,
concentrator
AGTR1 PDC CNTRL 1
Phasor data concentrator asserts control bit 1, as
received via the network.
as above
AGTR1 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network.
as above
AGTR1 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network.
↓
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network.
NOTE
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...