B-60
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
A963
Restricted Ground Fault 1 Slope
0 to 100
%
1
F001
40
A964
Restricted Ground Fault 1 Delay
0 to 600
s
0.01
F001
0
A965
Restricted Ground Fault 1 Reset Delay
0 to 600
s
0.01
F001
0
A966
Restricted Ground Fault 1 Block
0 to 4294967295
---
1
F300
0
A968
Restricted Ground Fault 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A969
Restricted Ground Fault 1 Events
0 to 1
---
1
F102
0 (Disabled)
A96A
...Repeated for Restricted Ground Fault 2
A974
...Repeated for Restricted Ground Fault 3
A97E
...Repeated for Restricted Ground Fault 4
A988
...Repeated for Restricted Ground Fault 5
A992
...Repeated for Restricted Ground Fault 6
IEC 61850 Received Analog Settings (Read/Write Setting) (32 modules)
AA00
IEC 61850 GOOSE Analog 1 Default Value
–1000000 to 1000000
---
0.001
F060
1000
AA02
IEC 61850 GOOSE Analog Input 1 Mode
0 to 1
---
1
F491
0 (Default Value)
AA03
IEC 61850 GOOSE Analog Input 1 Units
---
---
---
F207
(none)
AA05
IEC 61850 GOOSE Analog Input 1 Per-Unit Base
0 to 999999999.999
---
0.001
F060
1
AA07
...Repeated for IEC 61850 GOOSE Analog Input 2
AA0E
...Repeated for IEC 61850 GOOSE Analog Input 3
AA15
...Repeated for IEC 61850 GOOSE Analog Input 4
AA1C
...Repeated for IEC 61850 GOOSE Analog Input 5
AA23
...Repeated for IEC 61850 GOOSE Analog Input 6
AA2A
...Repeated for IEC 61850 GOOSE Analog Input 7
AA31
...Repeated for IEC 61850 GOOSE Analog Input 8
AA38
...Repeated for IEC 61850 GOOSE Analog Input 9
AA3F
...Repeated for IEC 61850 GOOSE Analog Input 10
AA46
...Repeated for IEC 61850 GOOSE Analog Input 11
AA4D
...Repeated for IEC 61850 GOOSE Analog Input 12
AA54
...Repeated for IEC 61850 GOOSE Analog Input 13
AA5B
...Repeated for IEC 61850 GOOSE Analog Input 14
AA62
...Repeated for IEC 61850 GOOSE Analog Input 15
AA69
...Repeated for IEC 61850 GOOSE Analog Input 16
AA70
...Repeated for IEC 61850 GOOSE Analog Input 17
AA77
...Repeated for IEC 61850 GOOSE Analog Input 18
AA7E
...Repeated for IEC 61850 GOOSE Analog Input 19
AA85
...Repeated for IEC 61850 GOOSE Analog Input 20
AA8C
...Repeated for IEC 61850 GOOSE Analog Input 21
AA93
...Repeated for IEC 61850 GOOSE Analog Input 22
AA9A
...Repeated for IEC 61850 GOOSE Analog Input 23
AAA1
...Repeated for IEC 61850 GOOSE Analog Input 24
AAA8
...Repeated for IEC 61850 GOOSE Analog Input 25
AAAF
...Repeated for IEC 61850 GOOSE Analog Input 26
AAB6
...Repeated for IEC 61850 GOOSE Analog Input 27
AABD
...Repeated for IEC 61850 GOOSE Analog Input 28
AAC4
...Repeated for IEC 61850 GOOSE Analog Input 29
AACB
...Repeated for IEC 61850 GOOSE Analog Input 30
AAD2
...Repeated for IEC 61850 GOOSE Analog Input 31
AAD9
...Repeated for IEC 61850 GOOSE Analog Input 32
IEC 61850 XCBR Configuration (Read/Write Settings and Commands) (6 modules)
AB00
Operand for IEC 61850 XCBR1.ST.Loc status
0 to 4294967295
---
1
F300
0
AB02
Command to Clear XCBR1 OpCnt (Operation Counter
0 to 1
---
1
F126
0 (No)
AB03
Operand for IEC 61850 XCBR Check Sync Release
0 to 4294967295
---
1
F300
0
AB05
Operand for IEC 61850 XCBR Open Interlock
0 to 4294967295
---
1
F300
0
AB07
Operand for IEC 61850 XCBR Close Interlock
0 to 4294967295
---
1
F300
0
AB09
Operand for IEC 61850 XCBR Pos ct1Model
0 to 4
---
1
F001
2
Table B–10: MODBUS MEMORY MAP (Sheet 52 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...