GE Multilin
T60 Transformer Protection System
5-181
5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6.3 DISTANCE
a) COMMON DISTANCE SETTINGS
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
The
DISTANCE SOURCE
identifies the signal source for all distance functions. The mho distance functions use a dynamic
characteristic: the positive-sequence voltage – either memorized or actual – is used as a polarizing signal. The memory
voltage is also used by the built-in directional supervising functions applied for both the mho and quad characteristics.
The
MEMORY DURATION
setting specifies the length of time a memorized positive-sequence voltage should be used in the
distance calculations. After this interval expires, the relay checks the magnitude of the actual positive-sequence voltage. If
it is higher than 10% of the nominal, the actual voltage is used, if lower – the memory voltage continues to be used.
The memory is established when the positive-sequence voltage stays above 80% of its nominal value for five power system
cycles. For this reason it is important to ensure that the nominal secondary voltage of the VT is entered correctly under the
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK
menu.
Set
MEMORY DURATION
long enough to ensure stability on close-in reverse three-phase faults. For this purpose, the maxi-
mum fault clearing time (breaker fail time) in the substation should be considered. On the other hand, the
MEMORY DURA-
TION
cannot be too long as the power system may experience power swing conditions rotating the voltage and current
phasors slowly while the memory voltage is static, as frozen at the beginning of the fault. Keeping the memory in effect for
too long may eventually lead to incorrect operation of the distance functions.
DISTANCE
DISTANCE
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
MEMORY
DURATION: 10 cycles
Range: 5 to 25 cycles in steps of 1
MESSAGE
FORCE SELF-POLAR:
Off
Range: FlexLogic operand
MESSAGE
FORCE MEM-POLAR:
Off
Range: FlexLogic operand
MESSAGE
PHASE DISTANCE Z1
MESSAGE
PHASE DISTANCE Z2
MESSAGE
PHASE DISTANCE Z3
MESSAGE
PHASE DISTANCE Z4
MESSAGE
PHASE DISTANCE Z5
MESSAGE
GROUND DISTANCE Z1
MESSAGE
GROUND DISTANCE Z2
MESSAGE
GROUND DISTANCE Z3
MESSAGE
GROUND DISTANCE Z4
MESSAGE
GROUND DISTANCE Z5
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...