CHAPTER 6: PROTECTION SETPOINTS
FREQUENCY ELEMENTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–149
SEMICYCLES SET
Range: 1 to 20 in steps of 1
Default: 3
This setting specifies a SET counter prior to picking up. When the frequency is detected
to be below the setting (and the rate of change is below the setting as well if in the DF/DT
Type), the element starts counting for however many consecutive half-periods (semi
cycles) it continues below the setting. If the SET counter is reached, the pickup signal of
the element is activated and the element starts the delay timer set independently for
each element. However, the invalid frequency measurement will not affect the SET
counter.
SEMICYCLES RESET
Range: 0 to 4 in steps of 1
Default: 0
If the frequency transiently restores and pickup conditions are not satisfied, the element
freezes the SET counter to pick up and starts counting the number of semi cycles to
reset the element. If the count of semi cycles to reset reaches the value set in the setting
SEMICYCLES RESET, then the element is reset. On the other hand, if the pickup conditions
are satisfied before reset, the element will continue the count of semi cycles to set from
where it was left. The invalid frequency measurement will not affect the SET counter.
The SEMICYCLES SET and SEMICYCLES RESET settings are common for the eight Fast
Underfrequency elements.
Path
:
Setpoints > Protection > Group 1(6) > Frequency > Fast Underfrequency > Fast
Underfreq1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
TYPE
Range: UF Only, UF and df/dt
Default: UF Only
This setting specifies the input to the element. The UF ONLY type uses only the
frequency value. The UF and DF/DT type considers both frequency and rate of change of
frequency (df/dt) as the input.
UNDERFREQENCY PICKUP
Range: 20.00 to 65.00 Hz in steps of 0.01 Hz
Default: 59.00 Hz
This setpoint sets the Underfrequency Pickup level.
RATE OF CHANGE PICKUP
Range: -10.00 to -0.10 Hz/sec in steps of 0.01 Hz/sec
Default: -0.75 Hz/sec
This setpoint sets the Rate of Change Pickup level.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
RESET DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...