CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
SYSTEM
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
5–71
Table 5-10: Breaker status with both contacts 52a and 52b configured
Figure 5-14: Breaker LEDs
Figure 5-15: Breaker Connected/Disconnected (Racked-In/Racked-Out) Detection
52a Contact Status
52b Contact Status
Breaker Status
Off
On
BKR Opened
On
Off
BKR Closed
On
On
BKR Unknown State
Off
Off
BKR Unknown State
SETPOINT
BKR 1 CONNECTED
FlexLogic operand =1,
Off = 0
FlexLogic operand status
AND
OR
FLEXLOGIC OPERANDS
BKR 1 Disconnected
FLEXLOGIC OPERANDS
BKR 1 Connected
894207A1.cdr