CHAPTER 6: PROTECTION SETPOINTS
ADMITTANCE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–123
B0 REV REACH
Range: -500.00 to 500.00 mS in steps of 0.01 mS
Default: -1.00 mS
This setting defines the pickup level of the protection criterion based on the neutral
susceptance. Neutral Admittance Ground Fault protection will operate after the set
Pickup Delay time when the neutral susceptance quantity, B0, lies below the reach level
defined by this setting. This setting is not applicable when the Direction setting is set to
Forward.
Depending on pick-up threshold (B0) and directional settings, susceptance
characteristics are as follows:
FASTPATH:
All the reach settings, for admittance, conductance, and susceptance, are expressed in
secondary Siemens.
MINIMUM CURRENT
Range: 0.02 to 1.00 x CT in steps of 0.01 mS
Default: 0.02 x CT
This setting specifies the minimum limit of the measuring process ground current to
activate Neutral Admittance Ground Fault protection. The element remains blocked until
the ground current value for building the protective criterion exceeds this minimum limit.
MINIMUM VOLTAGE
Range: 0.01 to 1.50 x VT in steps of 0.01 mS
Default: 0.01 x VT
This setting specifies the minimum limit of the measuring process ground voltage to
activate Neutral Admittance Ground Fault protection. The element remains blocked until
the ground voltage value for building the protective criterion exceeds this minimum
limit.
jB
G
jB
G
Operate
Block
jB
G
Operate
Block
Forward Direction Operate/Block Characteristic Reverse Direction Operate/Block Characteristic
Non-directional Operate/Block Characteristic
when B0 Fwd Reach
≥
B0 Rev Reach
B0 Fwd
Reach
B0 Rev
Reach
Block
B0 Fwd
Reach
Operate
B0 Rev
Reach
jB
G
Block
B0 Rev
Reach
Operate
B0 Fwd
Reach
Non-directional Operate/Block Characteristic
when B0 Fwd Reach
<
B0 Rev Reach
Block
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...