CHAPTER 8: CONTROL
SYNCHROCHECK (25)
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
8–37
If both Line and Bus sides are three-phase VTs, the VT types must match, i.e. either
both Line and Bus Volt inputs are Delta or both are Wye. If both sides are single-phase
Aux VT inputs, then both Aux VT connection types must match, i.e. if the Line side Aux
VT type is Vab, then the Bus side Aux VT type must be Vab. Aux VT connection “Vn” is
not a valid type for synchrocheck.
IMPORTANT:
Once the Synchrocheck function is programmed, it will perform a voltage input
selection check, to determine that these voltage magnitudes are not different by more
than 5% of each other. This check depends only on the settings entered for phase and
auxiliary VTs under Setpoints/System/Voltage Sensing menu. If the difference between
the both selected voltage inputs by calculation is bigger than 5%, the Synchrocheck
will not work.
For example, the phase VT can be set to Wye connection with secondary voltage of
66.4V. The Aux. VT can be connected between phase A to B with the secondary voltage
set to 115V. Then, one of the Synchrocheck inputs can be set as the Wye connected
phase voltage bank, and the other input can be the Aux. VT with voltage V
ab
. Since the
difference between the computed V
ab
input and the Aux. VT setting is 0%, the
Synchrocheck will work. However, if this difference is bigger than 5%, the
Synchrocheck will not work.
Path
:
Setpoints > Control > Synchrocheck 1(X)
FUNCTION
Range: Disabled, Enabled
Default: Disabled
BUS VOLTS INPUT
Range: dependant upon the order code
Default: J2-3VT
The setting provides selection of the Bus Volts input; either three-phase voltages from
the three-phase VTs connected to the relay, or a single voltage from the Auxiliary VT also
connected to the relay Aux VT input. The setup of these VTs is outlined under the
SYSTEM/VOLTAGE SENSING menu.
LINE VOLTS INPUT
Range: dependant upon the order code
Default: J2-Vx
The setting provides selection of the Line Volts input; either three-phase voltages from
the three-phase VTs connected to the relay, or a single voltage from the Auxiliary VT also
connected to the relay Aux VT input. The setup of these VTs is outlined under SYSTEM/
VOLTAGE SENSING menu.
MAX FREQ DIFFERENCE
Range: 0.01 to 5.00 Hz in steps of 0.01 Hz
Default: 0.20 Hz
The setting selects the maximum frequency difference in ‘Hz’ between the two sources.
A frequency difference between the two input voltage systems below this value is within
the permissible limit for synchronism.
MAX ANGLE DIFFERENCE
Range: 1 to 100° in steps of 1°
Default: 20°
The setpoint selects the maximum angular difference in degrees between the two
sources. An angular difference between the two input voltage phasors below this value
is within the permissible limit for synchronism.
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...