CHAPTER 1: INTRODUCTION
SPECIFICATIONS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
1–19
NEGATIVE SEQUENCE TIME OVERCURRENT (51_2)
Operating Parameter:.......................................I_2 (Fundamental Phasor Magnitude)
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................For 0.1 to 2.0 x CT:± 0.5% of reading or ±0.4% of rated,
whichever is greater
For > 2.0 x CT: ± 1.5% of reading
Curve Shape:.........................................................IEEE Extremely/Very/Moderately Inverse
ANSI Extremely/Very/Normally/Moderately Inverse
IEC Curve A/B/C and Short Inverse
IAC Extreme/Very/Inverse/Short Inverse
FlexCurve A/B/C/D
I
2
t, I
4
t, Definite Time
Curve Multiplier:...................................................0.05 to 600.00 in steps of 0.01
Reset Time: ............................................................Instantaneous, Timed
Curve Timing Accuracy: ..................................Currents > 1.1 x pickup: ± 3% of curve delay or ± ½ cycle
(whichever is greater) from pickup to operate
NOTE
NOTE:
Add 1.5 cycles to the curve time to obtain the TOC operating time, i.e., from fault inception
until operation.
NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT (50_2)
Current:....................................................................I_2 Fundamental Phasor Magnitude
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................For 0.1 to 2.0 x CT: ±0.5% of reading or ± 0.4% of rated,
whichever is greater
For > 2.0 x CT: ± 1.5% of reading
Pickup Time Delay:.............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay: .........................................0.000 to 6000.000 s in steps of 0.001 s
Overreach:..............................................................< 2%
Operate Time:.......................................................< 12 ms typical at 3 x Pickup at 60 Hz
< 15 ms typical at 3 x Pickup at 50 Hz
Timer Accuracy: ..................................................±3% of delay setting or ± ¼ cycle (whichever is greater) from
pickup to operate
NEUTRAL ADMITTANCE (21YN)
Operating Characteristic (Modes): ..............Admittance, Conductance and Susceptance
Directionality: .......................................................Non-directional, Forward and Reverse
Reach Admittance
(secondary Siemens): .................................0.00 to 500.00 mS in steps of 0.01
Reach Conductance\ Susceptance
(secondary Siemens): .................................-500.00 to 500.00 mS in steps of 0.01
Level Accuracy:....................................................±1% of Pickup or ±0.01 mS, whichever is greater
Pickup Delay: ........................................................0.000 to 600.000 s in steps of 0.001
Dropout Level: ......................................................0.000 to 600.000 s in steps of 0.001
Time Accuracy:....................................................±3% of delay setting time or ±20 ms, whichever is greater
Pickup:......................................................................< 12 ms typical at 3 x Pickup at 60 Hz
Minimum Current Supervision
Pickup:.................................................................0.02 to 1.00 x CT in steps of 0.01
Dropout: ..................................................................103% of pickup
Minimum Voltage Supervision
Pickup:.................................................................0.01 to 1.50 x VT in steps of 0.01
Dropout: ..................................................................103% of pickup
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...