6–120
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
ADMITTANCE
CHAPTER 6: PROTECTION SETPOINTS
ANGLE CORRECTION
Range: 0.0 to 359.0° in steps of 0.1°
Default: 0.0°
This setting specifies the correction angle between current and voltage.
In addition, this setting can be used to correct the relative polarity of the ground current
with respect to voltage. If the polarity of the current is reversed or not relative to voltage,
this setting can be used to change the polarity. When “180 deg” is selected, the
measured admittance Y0 is multiplied with -1 which corresponds to a 180 degree shift in
current direction.
Secondly, this angle can also be used to eliminate the angular errors of the voltage
transformer and/or current transformers (CT); measured phase angle deviations caused
by measuring inaccuracy of voltage transformers, can be eliminated by properly setting
this value.
jB
G
)
(
0
0
0
0
0
V
I
V
I
Y
)
(
180
0
0
0
0
0
V
I
V
I
Y
jB
G
Y0
Y0"
Y0'
Y0-
ƀ
c
Y0+
ƀ
c
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...