850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
OUTPUTS
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
If the selection for the Type setpoint is "Pulsed", the Trip and Close relay operation follows
the logic outlined below:
•
The Trip and Close relays reset after breaker is detected in a state corresponding to
the command. When a command is sent to one of these special relays, it remains in
operation until the requested change of the breaker state is confirmed and the
initiating condition has Reset.
•
If the command Resets without a change of breaker state, the output relay is Reset
after a default interval of 2 seconds.
•
If neither of the breaker auxiliary contacts. 52a or 52b, is programmed to a logic input,
the Trip Relay Resets after a default interval of 100 ms after the initiating input Resets.
The Close Relay is Reset after 200 ms.
•
The Seal-In Time setpoint is available only when the output relay is selected as
"Pulsed". In all other cases the Seal-In Time setpoint is hidden and deactivated. The
default setting for the seal-in time is 100 ms.
If the Type selected is "Latched", the output relay is energized by any Trip or Open
command and remains energized upon element dropout. Latched auxiliary outputs can be
reset with a reset command.If the type selected is "Self-Reset", the output relay is
energized when the corresponding element operates and it stays energized until the
element drops out.
OUTPUT RELAY AVAILABILITY
The output relays can be used for many different purposes such as opening and closing
breakers, contactors, switches, control of primary equipment such as motor, transformer,
generator, for blocking or supervision purposes, for interlocking, ect. To avoid using the
same output relay for two totally different actions, the 8series relays checks the
assignments of these output relays, and prevents their usage for some other actions. For
this purpose, the output relays that have been already assigned for some action, are
hidden from the menus of other elements. For example, if output relay 1 has been
assigned under Trip Relay Select setpoint to trip breaker 1, this output relay will be hidden
from the list of outputs available to select in the menu for opening or closing a Switch, and
vice versa. The table below defines the dependency of output relay availability based on
the first come-first serve principal.
52a Contact
Configured
52b Contact
Configured
Relay Operation
Yes
Yes
The Trip Relay and Close Relay continue operating until the
breaker is detected opened or closed using both 52a and 52b
contacts as per the breaker detection logic.
Yes
No
The Trip Relay continues operating until 52a indicates an
open breaker. The Close Relay continues operating until 52a
indicates a closed breaker.
No
Yes
The Trip Relay continues operating until 52b indicates an
open breaker. The Close Relay continues operating until 52b
indicates a closed breaker.
No
No
Trip Relay operates upon a Trip command and stays “high”
until the 100 ms default time expires. The Close Relay
operates upon a Close command and Resets after the 200 ms
time expires.
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...