6–98
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
VOLTAGE ELEMENTS
CHAPTER 6: PROTECTION SETPOINTS
Figure 6-44: Example of UV Reactive Power (27Q) applied for the generating feeder
NOTE
NOTE:
UV Reactive Power 1 (2 or 3) are associated with Breaker 1 and UV Reactive Power 4 (5 or 6)
are associated with Breaker 2. When the restoration function is enabled, respective closing
relays are used depending on the UV Reactive Power element instance.
Path
:
Setpoints > Protection > Group 1(6) > Voltage > UV Reactive Power 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
This setting provides the selection for the Phase to ground and Phase to phase voltages
for a Wye VT connection (phase to phase for delta connected VT connection.
SIGNAL INPUT
Range: Power 1, Power 2
Default: Power 1
This setting provides the power source selection. The selection for power comes from the
power sensing settings in system setup.
When Signal Input is programmed as Power 1, the element uses actual metering value
Pwr1 Reactive (Metering\Power 1). When the Signal Input is programmed as Power 2,
element uses actual metering value Pwr2 Reactive (Metering\Power 1).
VOLTAGE MODE
Range: Phase-to-ground, Phase-to-phase
Default: Phase-to-phase
This setting provides selections for Phase to ground and Phase to phase voltages for a
Wye VT connection (phase to phase for delta connected VT connection).
FASTPATH:
Setpoint Voltage Mode is only applicable when Phase VT Connection (under System >
Voltage Sensing > Ph VT Bnk1-J2) selection is Wye. This setting is hidden when the Phase
VT Connection selection is Delta.
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...