CHAPTER 6: PROTECTION SETPOINTS
CURRENT ELEMENTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–31
Ground Time Overcurrent Protection (51G)
The 850 is equipped with the Ground Time Overcurrent protection element. The settings of
this function are applied to the ground input current to produce Trip or Pickup flags. The
Ground TOC Pickup flag is asserted when the ground current is above the PKP value. The
Ground TOC Trip flag is asserted if the element stays picked up for the time defined by the
selected inverse curve and the magnitude of the current. The element drops from Pickup
without operation if the measured current drops below 97 to 98% of the Pickup value
before the time for operation is reached. When Definite Time is selected, the time for
Ground TOC operation is defined only by the TDM setting.
Path
:
Setpoints > Protection > Group 1(6) > Current > Ground TOC 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
SIGNAL INPUT
Range: dependant upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names
can be changed in Setpoints > System > Current Sensing > [Name] > CT Bank Name.
INPUT
Range: Phasor, RMS
Default: Phasor
PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
CURVE
Range: IEEE Extremely/Very/Moderately Inverse,
ANSI Extremely/Very/Normally/Moderately Inverse,
Definite time IEC A/B/C and Short Inverse,
IAC Extremely/Very/Inverse/Short Inverse
FlexCurve A/B/C/D, I2t, I4t
Default: IEEE, Moderately Inverse
TDM
Range: 0.05 to 600.00 in steps of 0.01
Default: 1.00
RESET
Range: Instantaneous, Timed
Default: Instantaneous
DIRECTION
Range: Disabled, Forward, Reverse or Disabled, Ntrl Dir OC [1-2] FWD, Ntrl Dir OC [1-2]
REV, Dependant upon order code
Default: Disabled
BLOCK
Range: Off, Any FlexLogic operand
Default: Off or PB 4 OFF (GND TRIP ENABLED), Dependant on order code
OUTPUT RELAY X
For details see
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...