9–24
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 9: FLEXLOGIC AND OTHER SETPOINTS
for switching-in/out transformer equipment. The setpoints of the FlexElement below reflect
detecting a 5°C degree temperature difference between the istalled RTDs measuring the
top and bottom oil temperatures:
•
Input 1(+): RTD 1 (top-oil)
•
Input 2(-): RTD 2 (bottom-oil)
•
Operating Mode: Absolute
•
Input Comparison Mode: Level
•
Direction: Over
•
Pickup: 0.050 pu
•
Hysteresis:
•
60.0%
With an RTD
BASE
= 100°C, the required temperature difference of 5°C, would be computed
as a pickup value of 5°C/100°C = 0.050 pu.
If it is required to drop out the operation of the FlexElement when the temperature
difference becomes 2°C, the hysteresis would be calculated as 5°C/100°C - 2°C/100°C =
3°C/100°C = 0.03 pu. Therefore:
Hysteresis = (0.03 pu *100)/0.05 = 60%
High Breaker Arcing current detection
High breaker arcing current can be detected by using a FlexElement during the opening of
a breaker. One or more FlexElements can be configured for detecting levels of maximum
arcing current during the tripping of a particular breaker, and give an indication for the
health of the breaker.
The base unit for the breaker arcing current is programmed in the relay as: BASE = 2000
kA
2
*cycle
•
Input 1(+): Total Arcing Current
•
Input 2(-): Off
•
Operating Mode: Absolute
•
Input Comparison Mode: Level
•
Direction: Over
•
Pickup: 2.500 pu
•
Hysteresis: 0.0 %
To configure the pickup setpoint for a total arcing current of 5000kA
2
/cycle, the per-unit
pickup value can be calculated as follows:
Pickup = 5000kA
2
*cycle/2000 kA
2
*cycle = 2.500 pu
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...