CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
5–35
IEC 60870-5-103
The point map for the 103 is different from the one shared by the IEC104 and DNP
protocols. IEC 60870-5-103 serial communications protocol is supported on the rear RS485
port only.
The DNP, IEC 103 and Modbus cannot be enabled simultaneously. Only one instance of
DNP3.0, IEC 103 or Modbus can run on the RS485 serial port.
PATH:
SETPOINTS > DEVICE > COMMUNICATIONS > IEC 60870-5-103 PROTOCOL
IEC103 Common ASDU Addrs
Range: 0 to 254 in steps of 1
Default: 0
IEC103 Sync Timeout
Range: 0 to 1440 minutes in steps of 1 min
Default: 0 min
IEC103 Activity Timeout
Range: 0 to 3600 seconds in steps of 1 s
Default: 0 s
All binary inputs are configured from FlexLogic operands. For a complete list, see Format
Code FC142.
FASTPATH:
Pay attention when configuring the function type and information number of the different
points, because they must be unique. There is no mechanism in the EnerVista 8 Series
Setup software or the front panel HMI to detect duplication of the information index.
FASTPATH:
The IEC 60870-5-103 point lists always begin with point 0 and end at the first “Off” value.
Since IEC 60870-5-103 point lists must be in one continuous block, any points assigned
after the first “Off” point are ignored.
IEC 61850
The optional communications processor supports both the IEC61850 GOOSE and IEC
61850 MMS Server service as per IEC 61850 standard Ed. 2. The GOOSE messaging service
provides the 850 unit the ability to Publish/Subscribe Digital Input Status and its Quality
and Timestamp to/from other IEDs with supporting GOOSE messaging service, while the
server support allows remote control center, RTU/Gateway, local HMI or other client role
devices access to the relay for monitoring and control. The configuration of IEC61850
services is accomplished using the 850 configuration software, EnerVista 8 Series
Setup software. A rebooting MUST be done before any changes made take affect.
The IEC 61850 Configurator
The 850 supports the IEC 61850 protocol which is identified by order code option “
2E
”.
The IEC 61850 configurator is found in both the online and offline section of the EnerVista
8 Series Setup software for configuring the online 850 and offline 850 settings file
respectively.
Online and Offline Setup
ONLINE SETTINGS FILE
Two options are available to configure the relay’s online settings file.
1.
Configuration
–
Configure the 850 (having order code option: IEC 61850) through the Device Setup
or Quick connect screen.
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...