6–72
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CURRENT ELEMENTS
CHAPTER 6: PROTECTION SETPOINTS
Figure 6-28: Broken Conductor Protection logic diagram
LED: PICKUP
Current Inputs
Negative Current (I2)
Positive Current (I1)
SETPOINTS
BLOCK:
Of
f=0
AND
SETPOINTS
BROKEN CONDUCT
OR
FUNCTION:
Disabled
T
rip
Alarm
Latched
Alarm
Configurable
OR
AND
SETPOINTS
BROKEN CONDUCT
OR
I_1 MIN:
|I_1| > I_1 MIN
RUN
SETPOINTS
BROKEN CONDUCT
OR
PICKUP
DELA
Y
:
2 cyc
0
Broken Cond OP
FlexLogic Operands
Broken Cond PKP
AND
AND
AND
Command
RESET
S
LA
TCH
Set-
Dominant
R
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
Phase
A
Current
(IA)
Phase B Current (IB)
Phase C Current (
IC
)
|IA| < I_1 MIN
|IC| < I_1 MIN
|IB| < I_1 MIN
|IA
’| - |IA| > 0.05pu
|IC’| - |IC| > 0.05pu
|IB’| - |IB| > 0.05pu
I’ is
4 cycles old
SETPOINTS
BROKEN CONDUCT
OR
I_1 MAX:
|I_1| < I_1 MAX
BROKEN CONDUCT
OR
I_2/I_1 RA
TIO
:
|I_2|/|I_1| > RA
T
IO
BROKEN CONDUCT
OR
I_1 MIN:
AND
AND
RUN
OR
OR
AND
t
PKP
0
SETPOINTS
OUTPUT
RELA
YS
(3-7):
Do Not Operate, Operate
SETPOINTS
SIGNAL
INPUT
:
CT Bank
1 -
J1
894043A2.cdr
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...