CHAPTER 9: FLEXLOGIC AND OTHER SETPOINTS
FLEXLOGIC
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
9–9
Phase TOC
Ph TOC 1 PKP A
Ph TOC 1 PKP B
Ph TOC 1 PKP C
Ph TOC 1 PKP
Ph TOC 1 OP A
Ph TOC 1 OP B
Ph TOC 1 OP C
Ph TOC 1 OP
Ph TOC 2
Phase A of phase time overcurrent 1 has picked up
Phase B of phase time overcurrent 1 has picked up
Phase C of phase time overcurrent 1 has picked up
At least one phase of phase time overcurrent 1 has picked up
Phase A of phase time overcurrent 1 has operated
Phase B of phase time overcurrent 1 has operated
Phase C of phase time overcurrent 1 has operated
At least one phase of phase time overcurrent 1 has operated
The same set of operands as per Phase TOC 1
Phase IOC
Ph IOC 1 PKP A
Ph IOC 1 PKP B
Ph IOC 1 PKP C
Ph IOC 1 PKP
Ph IOC 1 OP A
Ph IOC 1 OP B
Ph IOC 1 OP C
Ph IOC 1 OP
Ph IOC 2 OP
Phase A of phase IOC 1 has picked up
Phase B of phase IOC 1 has picked up
Phase C of phase IOC 1 has picked up
At least one phase of phase IOC overcurrent 1 has picked up
Phase A of phase IOC 1 has operated
Phase B of phase IOC 1 has operated
Phase C of phase IOC 1 has operated
At least one phase of phase IOC 1 has operated
The same set of operands as per Phase IOC 1
Phase Directional OC
Ph Dir OC REV A
Ph Dir OC REV B
Ph Dir OC REV C
Ph Dir OC REV
Phase A current in reverse direction
Phase B current in reverse direction
Phase C current in reverse direction
At least one phase current in reverse direction
Phase UV
Ph UV 1 PKP
Ph UV 1 PKP A
Ph UV 1 PKP B
Ph UV 1 PKP C
Ph UV 1 OP
Ph UV 1 OP A
Ph UV 1 OP B
Ph UV 1 OP C
Ph UV 2
At least one phase of phase undervoltage 1 has picked up
Phase A of phase undervoltage 1 has picked up
Phase B of phase undervoltage 1 has picked up
Phase C of phase undervoltage 1 has picked up
At least one phase of phase undervoltage 1 has operated
Phase A of phase undervoltage 1 has operated
Phase B of phase undervoltage 1 has operated
Phase C of phase undervoltage 1 has operated
The same set of operands as per Phase UV 1
Phase OV
Ph OV 1 PKP
Ph OV 1 PKP A
Ph OV 1 PKP B
Ph OV 1 PKP C
Ph OV 1 OP
Ph OV 1 OP A
Ph OV 1 OP B
Ph OV 1 OP C
Ph OV 2
At least one phase of phase overvoltage 1 has picked up
Phase A of phase overvoltage element 1 has picked up
Phase B of phase overvoltage element 1 has picked up
Phase C of phase overvoltage element 1 has picked up
At least one phase of phase overvoltage 1 has operated
Phase A of phase overvoltage element 1 has operated
Phase B of phase overvoltage element 1 has operated
Phase C of phase overvoltage element 1 has operated
The same set of operands as per Phase OV 1
Pole Discordance
Pole Discord 1 OP
External PD 1 OP
Contact PD 1 OP
Current PD 1 OP
PD1 - A Fail to Open
PD1 - B Fail to Open
PD1 - C Fail to Open
PD1 - A Fail to Cls
PD1 - B Fail to Cls
PD1 - C Fail to Cls
Pole Discordance 1 operated
External pole discordance 1 detection operated
Contacts based detection of pole discordance 1 operated
Currents based detection of pole discordance 1 operated
Pole Discordance 1 Phase A failed to open
Pole Discordance 1 Phase B failed to open
Pole Discordance 1 Phase C failed to open
Pole Discordance 1 Phase A failed to close
Pole Discordance 1 Phase B failed to close
Pole Discordance 1 Phase C failed to close
Power Factor
PF 1 Switch-In
PF 1 Switch-Out
PF 1 Switch-In OP
PF 1 Switch-Out OP
PF 2
The measured power factor has crossed the Switch-in setpoint
The measured power factor has crossed the Switch-Out setpoint
The PF1 Switch-In element operated
The PF1 Switch-Out element operated
The same set of operands as per PF 1
Pulse Output
Pos Wthrs Pulse OP
Neg Wthrs Pulse OP
Pos Varh Pulse OP
Neg Varh Pulse OP
Positive Watthours pulse occurs at the end of the programed energy
increment
Negative Watthours pulse occurs at the end of the programed energy
increment
Positive VARhours pulse occurs at the end of the programed energy
increment
Negative VARhours pulse occurs at the end of the programed energy
increment
Relay Service
In-Service
The relay is In-Service
Remote Input
Rem Ip # ON
Rem Ip # OFF
# – any remote input number
Remote Modbus Device
FlexLogic Operand [X] On
FlexLogic Operand [X] Off
[X] - the element number. Note the operand name will change depending
on what is programmed.
ELEMENT
OPERANDS
EVENT DESCRIPTION
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...