CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
5–19
FLEXLOGIC OPERANDS
The following operands are added for CyberSentry.
Communications
8 Series relays have a two-stage communications capability. The base CPU supports
Modbus protocol through the Ethernet, USB, serial and WiFi port. In addition, the base CPU
also supports IEC 103, DNP serial, DNP TCP/IP, and TFTP protocol. Once the
communications module option is added to the base, the base Ethernet port becomes
disabled but the two Ethernet ports on the communications module have enhanced
communications capabilities such as IEC61850, IEC62439 parallel redundancy protocol
(PRP) and IEEE 1588 Precision Time Protocol (PTP). The communications CPU also supports
Modbus TCP, IEC 104, DNP TCP, TFTP, SFTP, and SNTP protocol.
Modbus Protocol
All Ethernet ports and serial communication ports support the Modbus protocol. The only
exception is if the serial port has been configured for DNP or IEC 60870-5-103 operation
(see descriptions below). This allows the EnerVista 8 Series Setup software (which is a
Modbus master application) to communicate to the 850.
The 850 implements a subset of the Modicon Modbus RTU serial communication standard.
The Modbus protocol is hardware-independent. That is, the physical layer can be any of a
variety of standard hardware configurations. This includes USB, RS485, fiber optics, etc.
Modbus is a single master / multiple slave type of protocol suitable for a multi-drop
configuration.
The 850 is always a Modbus slave with a valid slave address range 1 to 254.
DATA FRAME FORMAT AND DATA RATE
One data frame of an asynchronous transmission to or from an 850 typically consists of 1
start bit, 8 data bits, and 1 stop bit. This produces a 10-bit data frame. This is important for
transmission through modems at high bit rates. Modbus protocol can be implemented at
any standard communication speed. The 850 supports operation at 9600, 19200, 38400,
57600, and 115200 bps baud rate. The USB interface supports ModBus TCP/IP.
FUNCTION CODE SUPPORTED
The following functions are supported by the 850:
•
FUNCTION CODE 03H - Read Setpoints
•
FUNCTION CODE 04H - Read Actual Values
•
FUNCTION CODE 05H - Execute Operation
•
FUNCTION CODE 06H - Store Single Setpoint
•
FUNCTION CODE 07H - Read Device Status
CLEAR_EVENT_RECORDS,
ORIGIN, TIMESTAMP:
Warning (4)
Clear event records command was issued.
CLEAR_TRANSIENT_RECORDS,
ORIGIN, TIMESTAMP:
Notice (5)
Clear transient records command was
issued.
CLEAR_FAULT_REPORTS,
ORIGIN, TIMESTAMP:
Notice (5)
Clear fault reports command was issued.
CyberSentry FlexLogic Operand
Description
AUTHENTICATION FAIL
Operand set for Failed Authentication self test and
alarm
UNAUTH SETTING CHANGE ATTEMPT
Operand set for unauthorized setting change action
RADIUS SRV UNAVAILABLE
Operand set for RADIUS servers unavailable self test
Event Record
Level
Description
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...