8–82
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTORECLOSE
CHAPTER 8: CONTROL
state has to be determined by the 52a/b contact inputs wired to the 850 ) to determine if
a manual CLOSE has occurred. The 850 uses the detection of a manual CLOSE to disable
the Autoreclose scheme to prevent reclosing on to a fault.
Also, if the Autoreclose scheme is in the Lockout state, a successful manual CLOSE
results in the Autoreclose scheme being reset if setpoint RST LOCKOUT ON MANUAL CLS
is set to ON, and Autoreclose is enabled after the BLK TIME UPON MANUAL CLS time has
expired.
When set to “OFF,” only CLOSE commands sent via the 850 front panel is considered to
be a manual CLOSE for the Autoreclose scheme logic.
BLK TIME UPON MANUAL CLS
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 10.000 s
The Autoreclose scheme is disabled for a programmable time delay after the breaker is
manually closed. This prevents reclosing on to a fault after a manual CLOSE. This delay
must be longer than the slowest expected Trip from any protection not blocked after
manual closing. The timer starts timing when the timer input drops out. After a manual
CLOSE and when this timer expires, the Autoreclose scheme is automatically reset if
setpoint RST LOCKOUT ON MANUAL CLS is set to ON. The Lockout is cleared and the shot
counter is set to 0.
RST LOCKOUT ON MANUAL CLS
Range: Off, On
Default: Off
The setpoint allows the Autoreclose scheme to be reset from Lockout if the breaker is
manually closed, regardless of whether the breaker remains closed or not. This setting
overrides RST LOCKOUT IF BKR CLOSED.
RST LOCKOUT IF BKR CLOSED
Range: Off, On
Default: Off
The setpoint allows the Autoreclose scheme to be reset from Lockout if the breaker has
been manually closed and stays closed for a pre-set time. In order for this setting to be
effective RST LOCKOUT ON MANUAL CLS should be disabled.
RST LOCKOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 60.000 s
The setting establishes how long the breaker stays closed after a manual CLOSE
command, in order for the Autorecloser to reset from Lockout.
MANUAL RESET FROM LOCKOUT
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
that resets the Autoreclose scheme from the Lockout condition. Typically this is a local
or remote manual reset from Lockout.
ADD DELAY
Range: Off, Any FlexLogic operand
Default: Off
The setting selects the FlexLogic operand, digital input, virtual input or remote input that
introduces an additional delay to the initially set Dead Times (1 through 4). When this
setting is OFF, the delay is by-passed.
Содержание Multilin 850
Страница 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Страница 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Страница 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Страница 268: ...5 106 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL OUTPUTS CHAPTER 5 DEVICE SYSTEM INPUT AND OUTPUT SETPOINTS ...
Страница 420: ...6 152 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FREQUENCY ELEMENTS CHAPTER 6 PROTECTION SETPOINTS ...
Страница 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Страница 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...