5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 254/1016 Operation Manual
5-3
FM
P/N: 06-326-2
Rev 6, 09/2015
5.4.1.1
DEVICE TYPE, LOCATION AND LED DIAGNOSTICS
The Device Type Diagnostic screen allows you to compare the type of addressable device held in the panel’s
configuration at a specific address to the type of device present/found on the signaling line circuit (SLC).
From the Device Diagnostic Menu, press the F1 button to display the Device Loc & LED Diagnostic screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
L O O P : N
A D R : 0 0 1 - 0 2 0 D
B
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
C
C O N F I G U R E D D E V
T Y P E
D
P R E S E N T D E V I C E T Y P E
Exhibit 5-3: Device Type Diagnostic Screen
•
Row A (LOOP) - Allows you to select the loop number, represented by ‘
N
’. Use the
◄► buttons
to position the cursor under the field; then press the
+/-
buttons to change to desired loop (1-4).
•
Row A (ADR) - Allows you to select the address range to display in groups of 20. Use the
◄►
buttons to position the cursor under the first digits (001 in this case); then press the
+/-
buttons to
increment/decrement the group selection.
•
Row A (D) - Allows you to select the data type that will be displayed on Row D. Use the
◄►
buttons to position the cursor under the field; then press the
+/-
buttons to increment/decrement
the selection.
•
D - Displays the device typepresent/found connected on the addressable loop at the specific
address. Same device types as shown in Row C description below. Press the F1 button to
view the device missing counter for the device at the cursor position. Press the F1 button
again to return to previous screen.
L – Allows you to light the LED for the device (red/green flash). To light the device LED, use
the ◄► buttons to position the cursor under the desired address on Row D. Toggle the LED
status by pressing the +/- button at the specific address location. An “L” will be displayed to
indicate that the device LED is lit. Press the +/- button again to turn off the LED.
R – Displays an “R” under each device address that has had its memory map read into the
panel memory.
d – Displays a “d” under each device address that has been disabled.
•
Row B - These numbers act as placeholders for the range of addresses selected in Row A.
•
Row C - Displays the type of device programmed in the configuration for the specific address
displayed:
P = Photo
H = Heat
F = FAAST
D = DUCT
M = Monitor, 4”
- = Unknown
Y = Relay
m = Mini Monitor
A = Relay (AHU shutdown)
U = Photo/Heat
I = Ion
T = Pull Station
2 = Dual Monitor
C = Control
Z = Conventional Zone
Note:
The panel loads this screen upon reset and does not provide live updates as loop
changes are made. Therefore, the panel must be reset in order to update this screen if wiring
or SLC status is modified.
•
Row D - Information displayed in this row is determined by the “Data Type” selection made on the
far right of Row A.