3.0 SYSTEM OPERATION
UL S2203
CyberCat 254/1016 Operation Manual
3-11
FM
P/N: 06-326-2
Rev 6, 09/2015
3.3.7
SUPERVISORY STATE
The Supervisory State may be activated by any input configured for Supervisory. These inputs are typically
connected to Sprinkler system Tamper or Low Air Pressure input contacts. Upon entering the Supervisory
State the control panel does the following:
1. SUPERVISORY LED flashes.
2. Panel sounder activates on & off (warbles).
3. LED on active device will turn on (Red) to indicate its active status. It will light its remote LED as
programmed, if connected.
4. System Supervisory relay (P2) activates.
5. Associated system outputs (notification and control) will activate if programmed for specific Zone and
State of activated device.
6. Sends Supervisory message to remote displays, history buffer, printers, PC monitoring stations, and
DACT.
7. Displays Supervisory event on the LCD display for 100 seconds as follows; then switches to the
System Status Display if all events are restored and no buttons are pressed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
S U P E R V I S O R Y I N P U T
B
C U S T O M M E S S A G E L - A D R
C
H H : M M : S S A M M / D D / Y Y Y Y
D
E V E N T X X X X O F Y Y Y Y
Exhibit 3-8: Supervisory Display
•
Row A – Displays the device type associated with the Supervisory event
•
Row B – Displays the 20 character custom message for the device
•
Row C – Displays the Time and Date of Event
•
Row D – Displays the event number (XXXX) and the total number of current events (YYYY)
How to respond to a Supervisory Event:
1. Press the ACKNOWLEDGE button to silence the panel sounder only. The panel SUPERVISORY LED
will change from flashing to steady. The control panel will send an acknowledge message to remote
displays, history buffer, printers, PC monitoring stations, and DACT.
2. Press the F1 button to toggle Rows A and B on display to show the Panel-Loop-Address of active device.
3. Press the F2 button to toggle Rows C and D on display to show the extra 40 characters of the devices
custom message.
4. Press the SILENCE button to silence the panel sounder and any activated outputs that are programmed
as silenceable. The panel SUPERVISORY LED will change from flashing to steady. The control panel
will send a silence message to remote displays, history buffer, printers, PC monitoring stations, and
DACT.
5. Investigate the cause of the Supervisory event. Contact Fike for a complete listing of system event
messages and suggested corrective actions.
6. Correct the condition causing the Supervisory event; the panel will require reset to restore the system to
Normal (non-latching events).
7. For latching events, press the system RESET button to clear the event and return the panel to Normal.
Note:
Supervisory inputs may be configured for latching or non-latching. Latching troubles require reset
of the panel to clear the fault.
Note:
When a Zone Disable is active, it also automatically creates a Supervisory in the disabled zone.