5.0 SYSTEM DIAGNOSTICS
5-26
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
5.8.3 PLAY MESSAGE ID STATUS
The Play Message ID Status screen allows you to view the voice message numbers being transmitted by the
panel to the amplifiers. From the Diagnostic Menu 5 screen, press the F3 button to view the Play Message
ID Status screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A C T I V E M E S S A G E I D
B
Z O N E : 0 0 0 P : n n n S : x x x
C
S I L E N C E : O F F C I T Y : x
D
M N S R E S E T : n n n D I S A B L E
Exhibit 5-35: Play Message ID Status Screen
•
Row B (Zone) – Allows you to select the zone number (1 – 253) that will be displayed in Row B.
Use the +/- buttons to increment or decrement the zone number. The primary and secondary
message numbers for the selected zone will be shown as
P:nnn S:xxx
; where “nnn” and “xxx”
indicates the primary and secondary message numbers being played (Fire message = 1-16, MNS
message = 101-116).
•
Row C (Silence) – Indicates the silence status of the emergency communication system
(
ON/OFF
).
•
Row C (City) – Indicates the active city code being used by the voice system (if applicable). Valid
city code must be set in the panel’s configuration menus for this option to be visible.
•
Row D (MNS Reset) – Displays the MNS RESET countdown time.
•