6.0 SYSTEM MAINTENANCE
6-8
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Output Devices:
Each output device (i.e., control module, relay module and NAC) can be individually programmed to
participate in a system walk-test. Outputs will activate continuous (4 second duration) if programmed for the
specific Zone and State of the activated input device. This allows you to get an audible feedback from system
output devices each time a device is tested. By default, here is how the output devices come configured:
Control Module (P/N 55-042/55-047): Configured to respond to walk-test
Relay Module (P/N 55-043/55-048): Configured NOT to respond to walk-test
NAC1 (P10) and NAC2 (P11): Configured to respond to walk-test
A. PANEL WALK-TEST
When walk-test is executed from control panel, all devices programmed for walk-test will enter the walk-test
mode. Utilize the following procedure to perform the walk-test:
1. Enable walk-test operation from the control panel’s Maintenance Menu, F5-Maint > F4-WALKTS. If
the screen indicates walk-test DISABLED, utilize the panel’s Configuration menu F1-CONFIG > F6-
MENU 2 > F6-MENU 3 > F2-WALK to ENABLE walk-test operation for the panel. This requires an
administrator level password to change.
Note:
Detectors programmed for walk-test with IR will automatically issue a TEST ALARM
message upon activation of the walk-test mode through the control panel. Detectors will indicate
that they are in the walk-test mode by blinking their LEDs green then red continuously until the
control panel is reset.
2. Proceed to the first device to be tested.
3. Activate the device using canned smoke (detectors), manual activation (monitor modules) or DUCT
detector Remote Test Station (DUCT detectors). Verify alternating red and green LEDs on device.
4. Device broadcasts a TEST ALARM message. Message displays on the control panel LCD and
remote displays (if applicable).
5. Audible devices programmed to respond to this device’s activation turn on for 4 seconds
(continuous).
6. When test smoke clears from a detector or after a monitor module is deactivated, device being tested
will exit the test mode and the device LED returns to normal operation (flash green every 5 seconds).
7. After all devices are tested, download the panel history for testing records.
8. Reset the control panel to return it to normal operation. Panel will be reset automatically after a
maximum of 4 hours.