6.0 SYSTEM MAINTENANCE
UL S2203
CyberCat 254/1016 Operation Manual
6-11
FM
P/N: 06-326-2
Rev 6, 09/2015
6.4.2.2
MASS NOTIFICATION SYSTEM SILENCE
When the voice system amplifiers are activated for mass notification (MNS), they cannot be silenced using
the standard control panel silence switches. The MNS Silence function provides a means for the system
operator to silence the MNS system from the control panel (local or network). Silencing the MNS system
does not impact the operation of any active Fire Alarm inputs or outputs.
From the Maintenance Menu 2 screen, press the F2 button to silence the mass notification system.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
M A I N T E N A N C E M E N U 2
B
F 1 - M N S R S T F 4 - C F G R D
C
F 2 - * * * * * * * F 5 - F A A S T
D
F 3 -
S W T I M E
F 6 - A H U O N
Exhibit 6-19: MNS Silence Screen
•
Row C – Once F2 is pressed, the display will show “*******” for about one second. Any amplifiers
activated for MNS operation will silence. A system administrator level password is required for this
switch to function.
6.4.2.3
SWITCH OPERATION
When configured for City of Chicago operation, the CyberCat panel’s DRILL and SILENCE switches on the
main display are disabled in order to comply with local code requirements. The Switch Timeout screen allows
the user to temporarily enable the DRILL and SILENCE switches for a period of 0 – 24 hours for inspection
and testing purposes. This menu option only becomes visible if the panel is configured for COC operation
and a successful factory level password is entered. From the Maintenance Menu 2, press the F3 button to
access the screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
E N A B L E D R I L L / S I L E N C E
B
S W I T C H E S F O R :
C
0 0 H O U R S
D
Exhibit 6-20: Switch Timeout Screen
•
Row C - Use the
◄►arrow buttons to move the cursor under the field; then use the +/- buttons to
increment or decrement the field between 0 and 24 hours. The panel must be reset for the
switches to become operable. The switch will return to their normal, disabled state after the
countdown timer expires or the panel is reset.
Note:
Other system switches configured for Drill and Silence operation are not affected by this operation.